APPENDIX E: EtherNet/IP
TM
COMMUNICATIONS
IS-300CR INVERTER POWER SUPPLY
E-24
990-418
IO Read / Write Control Tags
ioControl.com.writeToIS800
Write request flag. Set this flag to 1 when the screen data is
populated and ready to be written to the IS-300CR. After the
data is written, this flag will get reset back to 0. The PLC
program should also monitor for the ioControl.com.writeNakError
flag for write failure/error.
ioControl.com.readFromIS800
Read request flag. Set this flag to 1 to request the reading of the
schedule/screen data. After the data is read, this flag will get reset
back to 0.
ioControl.com.errorResetComm
Error reset request flag. Set this flag to 1 to request a reset of the
IS-300CR error via serial communication channel. IS-300CR
error can also be reset via the IS-300CR digital input bit (refer to
the digital input definition below). After the error reset command
is written, this flag will get reset back to 0.
ioControl.com.prepareWriteData
This tag is to request the screen data be written to the ASCII tag
ioControl.par.dataToWriteToIS800 for preview and debugging
purposes.
ioControl.com.writeNakError
Flag which indicates when there is a screen data write failure to
IS-300CR.
Digital Output Tags
The digital output tags are inputs into the IS-300CR Inverter Power Supply