208
••••
Siemens
QUICKDESIGNER
Simatic TI 305
Simatic TI 305 Tag Variable Table
Device
Address
Data
Data
Data
Data
Data
Bit
Read
Description
Prefix
Range
Range
Range
Format
Width
Word
write
/ Write
& Notes
Min. Max. Order (y/n/rmw)
32 bit types
RD(2)
400-576
-1E+08
1E+08
S (1)
32
norm
n/a
R/W
Variable double
RD(2)
700-776
-1E+08
1E+08
S (1)
32
norm
n/a
R/W
Variable double
RL(2)
400-576
-1E+08
1E+08
S (1)
32
rev.
n/a
R/W
Variable long
RL(2)
700-776
-1E+08
1E+08
S (1)
32
rev.
n/a
R/W
Variable long
RF
400-576
-1E+08
1E+08
D
32
norm
n/a
R/W
Variable float
RF
700-776
-1E+08
1E+08
D
32
norm
n/a
R/W
Variable float
RR
400-576
-1E+08
1E+08
D
32
rev.
n/a
R/W
Variable real
RR
700-776
-1E+08
1E+08
D
32
rev.
n/a
R/W
Variable real
Words
R(2)
400-576
-32768
32767
S (1)
16
n/a
ww (3)
R/W
Variable (BYTE)
R(2)
600-677
0
9999
S (1)
16
n/a
ww (3)
R/W
Counter Acc,Timer Acc
R(2)
700-776
-32768
32767
S (1)
16
n/a
ww (3)
R/W
Variable Byte
Bits
IO
0-157
0
1
n/a
1
n/a
ww (3)
R/W
Input/Output (Bit)
IO
700-767
0
1
n/a
1
n/a
ww (3)
R/W
Input/Output (Bit)
C
160-377
0
1
n/a
1
n/a
ww (3)
R/W
Variable (Bit)
C
770-1077
0
1
n/a
1
n/a
ww (3)
R/W
Variable (Bit)
SR
500-577
0
1
n/a
1
n/a
ww (3)
R/W
Shift Register Bit
CT 600-677
0
1
n/a
16
n/a
n
R
Counter
Status
T
600-677
0
1
n/a
16
n/a
n
R
Timer Status
Note:
To specify bits for R, use the form
Raaa.bb
, where
aaa
means the word address
and
bb
means
the bit specification from 00-15. Writing to bits cause a word write.
Note 1:R location can be interpreted as Signed Integer, Unsigned Integer or BCD. The normal
interpretation of a R location is Signed Integer.
Note 2: The format qualifier changes the way this variable is read.
C Read or Write as BCD -9999 - 9999
I Read or Write as Signed Integer -32767 to 32768
U Read or Write as an Unsigned Integer 0 to 65535
Note 3: Writing to a bit cause a word write.
Address Format = Octal
The bit delimiter for R words is ( . ). The bit range is 0-15. The bit format is D (decimal). Other
variable types do NOT use bit delimiter.
The bit format for IO, C, and SR types is D (decimal)
The node ID delimiter for all types is ( _ ) . This is an underscore symbol. The Minimum Node ID is 1,
the Max Node ID is 90. The Node ID format is D (decimal).