AutoMate R-Net Gateway
The target display interface to the R-Net AutoMate Gateway is an asynchronous RS-232/422 serial port
with switch-selectible communication rates from 110 to 19.2 K Baud. The R-Net AutoMate Gateway
buffers messages in both directions allowing the transmission of messages on R-Net without waiting for
each response from each processor. The R-Net Gateway node number is assigned by the target display
from information found in the setup menus. The target display is responsible for originating and
receiving commands, for configuring the Gateway, for processing of response (ACK/NAK) frames, for
computing and verifying check sums, and for matching response to commands.
The R-Net Gateway does not retain its parameters when power is lost. The target display will set the
Gateway parameters if the power is lost and restored.
If you connect the target display to the Gateway using RS232-C, then the TCP cable HMI-CAB-C53
will work.
AutoMate R-Net Gateway Switch Settings
The following switch settings are required for connecting the Gateway to the target display.
Switch Position
ON
OFF
S1-1
Illegal
Asynchronous
S1-2
Illegal
Binary
S1-3
8 Data Bits
7 Data Bits
S1-4
Parity On
Parity Off
S1-5
Parity Even
Parity Odd
Baud Rate
S1-6
S1-7
S1-8
2400
OFF
OFF
ON
4800
ON
OFF
ON
9600
OFF
ON
ON
19200
ON
ON
ON
Switch Position
Function
ON
OFF
S2-4
Receive Clock
External
Internal
S2-5
I/O Port
RS422
RS232
S2-6
19.2K Baud
19737 Hz
18750 Hz
S2-7
NA
OFF
S2-8
NA
OFF