QUICKDESIGNER
Allen-Bradley
••••
25
Advanced Interface Converter AIC+
The AIC+ (Advanced Interface Converter, 1761-NET-AIC) provides a simplified, cost effective
solution for connecting RS-232 devices to DH-485 networks. Use the AIC+ for communications
connectivity with the MicroLogix 1000 DH-485 networking series controller. The AIC+ is also a good
choice for providing point-to-point RS-232 isolation.
The AIC+ can replace the 1747-PIC/1747-AIC combination when using channel 0 of an SLC 5/03 or
SLC 5/04 processor to access DH-485 or DF1 master-slave networks.
When connecting a QuickPanel to the AIC+ DH485 Port3, you must use the AB SLC DH485 protocol.
The drawing shows the setup dialog box for A-B SLC DH485
The Source ID is the target display address. The Destination ID is the PLC address where the target
display will get variable data. Enter Timeout in seconds. Click OK to return to the Project Setup dialog
box.
Serial Port Parameters
Click the Port button to display the Serial Parameters dialog. The port values are automatically set to
standard default values. The following settings are recommended for
AB SLC DH485.
Elect. Format
RS232
Baud Rate
19200
Data Bits
8
Parity
Even
Stop Bits
1
Handshake
None