Click OK to return to the Project Setup dialog box.
Setting the Mitsubishi Transmission Control Protocol
The Mitsubishi Computer Interface Module has multiple protocols available by changing the position
of the MODE switch. The target display uses Format 1 which is selected as position 1 for RS232 and
position 5 for RS422.
C
A
B
D
E
F
0
4
1
2
3
5
6
7
8
9
Mitsubishi Serial Communications Parameters
Communication parameters are selected by dip switch settings on the front of the module. Switches are
numbered SW11 to SW24.
SWITCH
FUNCTION
ON
OFF
SETTING
SW11
Protocol
RS422
RS232C
Off
SW12
Data Length
8 bits
7 bits
On
SW13,14,15
Baud Rate
see table
SW16
Parity Check
Yes
No
Off
SW17
Parity setting
Even
Odd
Off
SW18
Stop bit
2 bits
1 bit
Off
SW21
Sum check
Yes
No
On
SW22
Write during run
Allowed
Disallowed
On
SW23
Send Termination
Present
Absent
On
SW24
Rec Termination
Present
Absent
On
Baud Rate Table
300
600
1200
2400
4800
9600
19200
SW13
Off
On
Off
On
Off
On
Off
SW14
Off
Off
On
On
Off
Off
On
SW15
Off
Off
Off
Off
On
On
On
Mitsubishi Station Number
Each Communication Interface Module has a unique station number selected by switches X10 and X1.
The range of station numbers is 0 to 31 decimal.
0
4
1
2
3
5
6
7
8
9
X10
0
4
1
2
3
5
6
7
8
9
X1