QUICKDESIGNER
PLC Direct
••••
177
DL340 Cable
The DL340 has two RJ11 ports, both supporting DirectNET protocol up to 38K Baud. The QuickPanel
does not support 38K Baud so make sure the baud rate on the DL340 is set to the same setting as the
QuickPanel. The top RJ11 port is designated Port 1 and is a slave only port. The bottom port,
designated Port 2, can be set up as a DeviceNET Slave or Master. If you use Port 2, it must be
configured as a Slave port. The hardware switches on the module determine the configuration for Port
2. The DL340 is shown below.
DL340
RUN
CPU
PWR
BATT
PORT1
TX/RX
RS232C
FIXED
USER
PRG
PORT2
TX/RX
Use the HMI-CAB-C103 Cable for connecting a QuickPanel to a Direct Logic DL340.
TO TCP DEVICE
TO PLC DIRECT
DL 305
2
5
-PI
N
MAL
E
4-PIN MODULAR
PHONE CONNECTOR
HMI-CAB-C103/A
red
black
TOP
1
SHIELD
white
5
4
1
2
3
4
2
3
7
25-PIN MALE
green
DL350 Cable
The DL350 has a 6P6C Phone Jack supporting RS232C and is marked PORT1. A 25-pin D-shell
Connector supporting RS232C/RS422 is marked PORT2. Both ports support DirectNET. If you decide
to use Port 2, it must be configured as a DeviceNET Slave port. The hardware switches on the module
determine the configuration for Port 2. The DL350 is shown below.
DL350
RUN
CPU
RX1
RX2
PWR
BATT
TX1
TX2
PORT1
RUN
TERM
STOP
BATT
PORT2
D3-350 CPU