138
Rockwell Automation Publication 520-UM002B-EN-E - December 2017
Appendix A
Supplemental Drive Information
Power Specifications
Watts Loss
PowerFlex 527 Estimated Watts Loss (Rated Load, Speed & PWM)
Voltage
Output Current (A)
Total Watts Loss
100...120V,
50/60 Hz 1-Phase
2.5
27.0
4.8
53.0
6.0
67.0
200...240V,
50/60 Hz 1-Phase
2.5
29.0
4.8
50.0
8.0
81.0
11.0
111.0
200...240V,
50/60 Hz 1-Phase
w/ EMC Filter
2.5
29.0
4.8
53.0
8.0
84.0
11.0
116.0
200...240V,
50/60 Hz 3-Phase
2.5
29.0
5.0
50.0
8.0
79.0
11.0
107.0
17.5
148.0
24.0
259.0
32.2
323.0
48.3
584.0
62.1
708.0
380...480V,
50/60 Hz 3-Phase
1.4
27.0
2.3
37.0
4.0
62.0
6.0
86.0
10.5
129.0
13.0
170.0
17.0
221.0
24.0
303.0
30.0
387.0
380...480V,
50/60 Hz 3-Phase
w/ EMC Filter
1.4
27.0
2.3
37.0
4.0
63.0
6.0
88.0
10.5
133.0
13.0
175.0
17.0
230.0
24.0
313.0
30.0
402.0
37.0
602.0
43.0
697.0
Summary of Contents for PowerFlex 527