Rockwell Automation Publication 520-UM002B-EN-E - December 2017
63
Configuring the PowerFlex 527 Drive with Integrated Motion
Chapter 3
•
GuardLogix safety network number
•
Path from the GuardLogix controller to the PowerFlex 527 drive.
•
Configuration signature
If any differences are detected, the connection between the GuardLogix
controller and the PowerFlex 527 drive is lost, and the yellow icon appears
in the controller project tree after you download the program.
5.
Click Advanced.
The Advanced Connection Reaction Time Limit Configuration dialog
box appears.
Analyze each safety channel to determine the appropriate settings. The
smallest Input RPI allowed is 6 ms. Selecting small RPI values consumes
network bandwidth and can cause nuisance trips because other devices
cannot get access to the network.
For more information about the Advanced Connection Reaction Time
Limit Configuration, see the GuardLogix 5570 Controllers User Manual,
publication
.
6.
Click OK to close the Advanced Connection Reaction Time Limit
Configuration dialog box.
7.
Click OK to close the Module Properties dialog box.
Your PowerFlex 527 drive appears
in the Controller Organizer under
the Ethernet controller in the I/O
Configuration folder.
8.
Proceed to
Continue Drive Configuration on page 64
to continue
configuring your drive.
Summary of Contents for PowerFlex 527
Page 4: ...4 Rockwell Automation Publication520 UM002B EN E December 2017 Summary of Changes Notes...
Page 8: ...8 Rockwell Automation Publication 520 UM002B EN E December 2017 Table of Contents Notes...
Page 173: ...Rockwell Automation Publication520 UM002B EN E December 2017 173 Notes...
Page 174: ...174 Rockwell Automation Publication 520 UM002B EN E December 2017 Notes...
Page 175: ......