96
Rockwell Automation Publication 520-UM002B-EN-E - December 2017
Chapter 4
PowerFlex 527 Integrated Safe Torque-Off
The cause of the fault can be read using an explicit message:
Safe Torque-Off Fault Type: MSG
Parameter
Value
Description
Service Code
0x0E
Get Attribute Single
Class
0x5A
Safety Stop Functions
Instance
1
Axis number
Attribute
0x108
STO Fault Type
Data Type
SINT
Unsigned Short Integer
Safe Torque-Off Fault Type: Values
Value
Definition
1
No Fault
3
Circuit Error
102
Hardwired Input Discrepancy
104
Hardwired Input in Network Mode