![Allen-Bradley PowerFlex 527 User Manual Download Page 106](http://html1.mh-extra.com/html/allen-bradley/powerflex-527/powerflex-527_user-manual_2900243106.webp)
106
Rockwell Automation Publication 520-UM002B-EN-E - December 2017
Chapter 6
Network Control of Safe Torque-Off
See
Reset Safe Torque-Off Fault Diagram on page 106
for an understanding of
the PowerFlex 527 STO Fault reset functionality.
Reset Safe Torque-Off Fault Diagram
Troubleshoot Network Safe Torque-Off
PowerFlex 527 Drive Troubleshooting
IMPORTANT
An STO Fault sets the Axis.SafetyFault tag. After the STO Fault is reset, a MAFR
command must be issued by the motion controller to clear the Axis.SafetyFault
tag to enable motion.
Drv:SO.SafeTorqueOff
Disable Torque
Permit Torque
Faulted
SO.ResetRequest
No Fault
No Fault
No Fault
Faulted (cleared by MAFR)
No Fault
Start Inhibited
Reset Not Required
Reset Not Required
Reset Required
Torque Disabled
Start Permitted
Torque Permitted
Torque Disabled
Torque Permitted
Drv:SO.ResetRequest
Drv:SI.TorqueDisabled
Drv:SI.SafetyFault
DrvSI:ResetRequired
Axis.SafetyFault
Axis.SafeTorqueOffActiveInhibit
Axis.SafetyFaultStatus
Axis.SafetyResetRequestStatus
Axis.SafetyResetRequiredStatus
Axis.SafeTorqueOffActiveStatus
Axis.SafeTorqueOffDisabledStatus
Axis.SafeTorqueOffFault
Permit Torque
Disable Torque
Exception Code on Drive Display
Fault Message
Logix Designer
Problem
Possible Solutions
SAFE FLT S01 - SAFETY CORE
INTERNAL
CPUWatchDogFault
(1)
Drive safety diagnostic detected
internal STO design failure.
•
Cycle power.
•
Return drive for repair if fault continues.
FLT AXIS FLT M28 - SAFETY COMM
SafetyModuleCommunication
ErrorFault
(1)
Drive safety diagnostic detected
internal STO design failure.
•
Cycle power.
•
Return drive for repair if fault continues.
SAFE FLT S03 - SAFE TORQUE OFF
(STO Fault Type = 3)
SafeTorqueOffFault
(2)
Drive safety diagnostic detected
internal STO design failure
•
Cycle power.
•
Execute STO function.
•
Return drive for repair if fault continues.
SAFE FLT S03 - SAFE TORQUE OFF
(STO Fault Type = 104)
SafeTorqueOffFault
(2)
Hardwired input energized in
network mode.
•
Remove power.
•
Remove any connection to hardwired
safety inputs.
•
Restore power.
INIT FLT M14 - INVALID SAFETY
FIRMWARE
InvalidSafeyFirmwareFault
(2)
The safety firmware is not compatible
with the drive firmware, or the main
safety firmware is missing.
•
Cycle power.
•
Upgrade drive firmware.
•
Return drive for repair if fault continues.
(1) Displayed in the LCD display as Module Fault.
Summary of Contents for PowerFlex 527
Page 4: ...4 Rockwell Automation Publication520 UM002B EN E December 2017 Summary of Changes Notes...
Page 8: ...8 Rockwell Automation Publication 520 UM002B EN E December 2017 Table of Contents Notes...
Page 173: ...Rockwell Automation Publication520 UM002B EN E December 2017 173 Notes...
Page 174: ...174 Rockwell Automation Publication 520 UM002B EN E December 2017 Notes...
Page 175: ......