286
Rockwell Automation Publication 750-IN001O-EN-P - October 2014
Chapter 5
I/O Wiring
Figure 145 - 460V MP-Series, HPK-Series, or Allen-Bradley 1326AB-Series Motor and a Stegmann
Rotary or Rotary Encoder connected via a 2090-CFBM7DF-CEAAXX (Non-Flex) or -CEAFXX (Flex)
Set Universal Feedback parameter P6 [FB0 Device Sel] or P36 [FB1 Device Sel]
to 2 “Hiperface SC.”
IMPORTANT
Do not use 120 Volts with the motor thermostat.
IMPORTANT
The Thermal Switch cannot be accessed using 2090-XXNFMP-SXX or 2090-
CFBM7XX series cables.
Universal Feedback Option
Module TB1
Stegmann
Encoder TB
B
A
D
C
L
N
WH/RD
RD
WH/GY
OR
BK/WH
BK
BK/WH
BK
WH/RD
RD
WH/GY
OR
WH/GN
GN
WH/GN
GN
REFSIN
+SIN
REFCOS
+COS
DATA- (RS485)
DATA+ (RS485)
SHIELD
POWER COMMON
POWER
OVERALL SHIELD
F
E
R TS+
S TS-
-Sn
+Sn
-Cs
+Cs
IS
OS
-Xc
-Xd
+Xd
-Hf
+Hf
5c
+5
+Xc
12c
-A
A
-B
B
-Z
Z
+12