266
Rockwell Automation Publication 750-IN001O-EN-P - October 2014
Chapter 5
I/O Wiring
Auxiliary Power Supply Option Module
Table 66 - TB1 Terminal Designations
A connector cable is provided with Auxiliary Power Supply option modules for
use in PowerFlex 753 drives. The cable is used to connect the module to the
backplane when installed on the upper control pod brackets.
Figure 133 - Auxiliary Power Supply Installation in PowerFlex 753 Drive (All Frames) and
PowerFlex 755 (Frame 1 Drives Only)
20-750-APS
Terminal
Name
Description
AP+
+24 Volt Auxiliary Power
Connections for customer supplied power supply:
24V DC ±10%, 3 A, PELV (Protective Extra Low
Voltage) or SELV (Safety Extra Low Voltage)
AP–
Auxiliary Power Common
Sh
Shield
Terminating point for wire shields when an EMC
plate or conduit box is not installed.
IMPORTANT
The Auxiliary Power Supply option module may be installed in any option port.
Due to its size, the module will extend over and block an adjacent port.
Therefore, installation in Port 8 is recommended.
Do not use the Auxiliary Power Supply option module with Frame 8 and larger
drives. Refer to
for information on connecting an external power
supply to Frame 8 and larger drives.
IMPORTANT
The connector cable is used with PowerFlex 755 Frame 1 drives. The cable is not
used with PowerFlex 755 Frame 2 and larger drives.
AP+
AP–
Sh
AP+
AP-
Sh
Summary of Contents for PowerFlex 20-750-20COMM
Page 1: ...PowerFlex 750 Series AC Drives Catalog Numbers 20F 20G 21G Installation Instructions...
Page 6: ...6 Rockwell Automation Publication 750 IN001O EN P October 2014 Notes...
Page 10: ...10 Rockwell Automation Publication 750 IN001O EN P October 2014 Preface Notes...
Page 218: ...218 Rockwell Automation Publication 750 IN001O EN P October 2014 Chapter 4 Power Wiring Notes...
Page 301: ......