I/O Wiring
Chapter 5
120V Output Wiring for Drive Control
The Common DC Input drive provides limited 120V control power for use with
the drive control pod option modules. For terminal block wiring specifications
see
Table 52 - TB5 Terminal Designations
Table 53 - TB5 Jumper Settings
Fixed I/O
Terminal
Name
Description
Rating
1
UPS 120VAC OUT HOT
Jumper combinations
select the source of the
120V AC output for drive
control. See
120V AC, 50/60 Hz,
0.4 A, 48 VA
Fusing: 1A, 600V,
Class CC, Time Delay
2
120VAC HOT
3
CONTROL 120VAC OUT HOT
4
UPS 120VAC OUT NEUTRAL
5
120VAC NEUTRAL
6
CONTROL 120VAC OUT NEUTRAL
7
120VAC OUT NEUTRAL
Drive supplied 120V AC
output for drive control.
8
120VAC OUT HOT
120V AC from Control Transformer
Factory Jumper Settings:
•
TB5-2 and TB5-3
•
TB5-5 and TB5-6
120V AC from User Supplied UPS
User Jumper Settings:
•
TB5-1 and TB5-2
•
TB5-4 and TB5-5
ATTENTION:
Hazard of personal injury or equipment damage exists if jumpers
are incorrectly set. Verify jumpers are set for control scheme used before
energizing the circuit.
1
2
3
4
5
6
7
8
2
3
5
6
1
2
3
4
5
6
1
2
3
4
5
6
7
8
120V AC Output Neutral
Hot
120V AC Input Neutral
Hot
1 A
N 120 240 T1
1KVA
SW2
8
7
TB5
TB2
1
2
4
5
1
2
3
4
5
6
1
2
3
4
5
6
7
8
120V AC Output Neutral
Hot
120V AC UPS Input Neutral
Hot
1 A
SW2
TB5
TB2
6
Summary of Contents for PowerFlex 20-750-20COMM
Page 1: ...PowerFlex 750 Series AC Drives Catalog Numbers 20F 20G 21G Installation Instructions...
Page 6: ...6 Rockwell Automation Publication 750 IN001O EN P October 2014 Notes...
Page 10: ...10 Rockwell Automation Publication 750 IN001O EN P October 2014 Preface Notes...
Page 218: ...218 Rockwell Automation Publication 750 IN001O EN P October 2014 Chapter 4 Power Wiring Notes...
Page 301: ......