Rockwell Automation Publication 750-IN001O-EN-P - October 2014
295
I/O Wiring
Chapter 5
Control Wiring - Current
Frame 8 Drives with Cabinet
Options
Frame 8 drives are shipped from the factory with control power set to 120V AC.
To change control voltage to 230V AC, move the jumper as shown.
Table 99 - Control Power for Customer Use Voltage Selection - Floor Mount Frame 8 Drives
Control terminal block TB4 is mounted on the inside right panel of the cabinet
options bay in current production drives. TB1 referenced in the illustrations
below resides on the main control board. See
Table 100 - TB4 Terminal Block Specifications
Figure 159 - Control Terminal Blocks TB3 and TB4 - Floor Mount Frame 8 Drives
120V AC, 60Hz, 4.2A (Factory Setting)
230V AC, 50Hz, 2.2A
Name
Wire Size Range
Torque
Strip
Length
Maximum
Minimum
Maximum
Recommended
Control Terminal Block TB3
4.0 mm
2
(12 AWG)
0.2 mm
2
(24 AWG)
0.5 N•m
(4.5 lb•in)
0.4 N•m
(3.5 lb•in)
7 mm
(0.28 in.)
Control Terminal Block TB4
4.0 mm
2
(12 AWG)
0.5 mm
2
(20 AWG)
0.5 N•m
(4.5 lb•in)
0.4 N•m
(3.5 lb•in)
8 mm
(0.32 in.)
TB3(H)
TB4(7)
FU12
600V AC, 3A, Class CC
TB3(H)
TB4(6)
FU12
600V AC, 6A, Class CC
Input/Output Contactor with or without X1 Option
TS1
Thermostat
TB6(1)
TB4(4)
TB4(10)
TB6(4)
TB6(3)
TB4(5)
TB6(2)
TB1(+24V)
TB1(Di 0dc)
13
14
TB3(1)
TB3(4)
M2/M4
21
22
TB3(2)
TB3(3)
M2/M4
Optional Devices
M2/M4
TB4(3)
A1
A2
TB4(2)
Contactor without X1 Option
M2/M4
TB4(3)
A1
A2
TB4(2)
Contactor with X1 Option
Customer Supplied
Control Circuit
TB3
TB4
Summary of Contents for PowerFlex 20-750-20COMM
Page 1: ...PowerFlex 750 Series AC Drives Catalog Numbers 20F 20G 21G Installation Instructions...
Page 6: ...6 Rockwell Automation Publication 750 IN001O EN P October 2014 Notes...
Page 10: ...10 Rockwell Automation Publication 750 IN001O EN P October 2014 Preface Notes...
Page 218: ...218 Rockwell Automation Publication 750 IN001O EN P October 2014 Chapter 4 Power Wiring Notes...
Page 301: ......