234
Rockwell Automation Publication 750-IN001O-EN-P - October 2014
Chapter 5
I/O Wiring
AC Input Drive Control and
Power Terminal Block
Figure 127 - Floor Mount Frames 8…10
Table 48 - TB2 Terminal Designations
Shunt Trip Contact Operation
A ground fault occurs when the input ground current exceeds the threshold set in
P16 [Gnd Cur Flt Lvl] on port 11 for five line cycles.
Fixed I/O
Terminal
Name
Description
Rating
Related
Param
1
SHUNT TRIP
COMMON
Output Relay common
125V AC, 10 A max.,
1250 VA Resistive Only
16 on
Port 11
2
SHUNT TRIP NO
Output Relay normally
open contact.
3
FAN 240VAC OUT
NEUTRAL
Connections for cooling
fans.
240V AC, 50/60 Hz, 1.4 A,
336 VA
4
FAN 240VAC OUT
HOT
AC Input Drive Control Panel
1
2
3
4