Rockwell Automation Publication 750-IN001O-EN-P - October 2014
203
Power Wiring
Chapter 4
Figure 107 - Option P3 or P5 Disconnect, Option P12 Output Contactor, and Option L2 or L4 Output
Reactor (Floor Mount Frame 8 Only)
No.
Name
Description
Recommended Torque
➊
R/L1, S/L2, T/L3
Three-phase input power connection.
Factory Installed
➋
PE
Three-phase input ground.
38.0 N•m (336 lb•in)
➌
PE
Three-phase motor ground.
38.0 N•m (336 lb•in)
➍
U/T1, V/T2, W/T3
Motor connection.
38.0 N•m (336 lb•in)
➍
ø15 (0.6)
4 Places
44.5
(1.75)
19.1
(0.75)
70.5
(2.80)
21.5
(0.85)
➋
➌
➊
Drive
Motor
P3 or P5
P12
L2 or L4
Output Terminal