Rockwell Automation Publication 750-IN001O-EN-P - October 2014
249
I/O Wiring
Chapter 5
Analog Voltage Input
Unipolar Speed Reference
0 to +10V Input
11-Series I/O Module TB1
•
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
•
Set Selection
Port 0: P545 [Spd Ref A Sel] = Port X (11-Series I/O Module): P50 [Anlg In0 Value]
•
Adjust Scaling
Port X (11-Series I/O Module): P51 [Anlg In1 Hi] = 10 Volt
Port X (11-Series I/O Module): P52 [Anlg In1 Lo] = 0 Volt
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
•
View Results
Port X (11-Series I/O Module): P50 [Anlg In0 Value]
Port 0: P592 [Selected Spd Ref]
Analog Current Input
Unipolar Speed Reference
0-20 mA Input
11-Series I/O Module TB1
•
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
•
Set Selection
Port 0: P545 [Spd Ref A Sel] = Port X (11-Series I/O Module): P50 [Anlg In0 Value]
•
Adjust Scaling
Port X (11-Series I/O Module): P51 [Anlg In0 Hi] = 20 mA
Port X (11-Series I/O Module): P52 [Anlg In0 Lo] = 0 mA or 4 mA
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
•
View Results
Port X (11-Series I/O Module): P50 [Anlg In0 Value]
Port 0: P592 [Selected Spd Ref]
Analog Voltage Output
±10V, 0…20 mA Bipolar
+10V Unipolar
11-Series I/O Module TB1
•
Configuration
Port X (11-Series I/O Module): P70 [Anlg Out Type], bit 0 = 0
•
Set Selection
Port X (11-Series I/O Module): P75 [Anlg Out0 Sel] = Port 0: P3 [Mtr Vel Fdbk]
•
Adjust Scaling
Port X (11-Series I/O Module): P78 [Anlg Out0 DataHi] = 60 Hz
Port X (11-Series I/O Module): P79 [Anlg Out0 DataLo] = 0 Hz
Port X (11-Series I/O Module): P80 [Anlg Out0 Hi] =10V/20 mA
Port X (11-Series I/O Module): P81 [Anlg Out0 Lo] = 0V/0 mA
•
View Results
Port X (11-Series I/O Module): P77 [Anlg Out0 Data]
Port X (11-Series I/O Module): P82 [Anlg Out0 Val]
2-Wire Control Non-
Reversing
24V DC internal supply
11-Series I/O Module TB1
•
Set Direction Mode
Port 0: P308 [Direction Mode] = 2 “Rev Disable”
•
Set Selection
Port 0: P163 [DI Run] = Port X (11-Series I/O Module): P1 [Dig In Sts], bit 0 = Input 0
•
View Results
Port X (11-Series I/O Module): P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]
11-Series I/O Module TB1 Wiring Examples (Continued)
Input/Output
Connection Example
Required Parameter Changes
Ai0–
Ai0+
Sh
Common
+
P5
1
2
P4
1
2
Ai0–
Ai0+
Sh
Common
+
P5
1
2
P4
1
2
Ao0–
Ao0+
Sh
+
–
Di0
Di0P
Stop-Run
P3
P8
3
1
3
1
Summary of Contents for PowerFlex 20-750-20COMM
Page 1: ...PowerFlex 750 Series AC Drives Catalog Numbers 20F 20G 21G Installation Instructions...
Page 6: ...6 Rockwell Automation Publication 750 IN001O EN P October 2014 Notes...
Page 10: ...10 Rockwell Automation Publication 750 IN001O EN P October 2014 Preface Notes...
Page 218: ...218 Rockwell Automation Publication 750 IN001O EN P October 2014 Chapter 4 Power Wiring Notes...
Page 301: ......