Rockwell Automation Publication 750-IN001O-EN-P - October 2014
275
I/O Wiring
Chapter 5
Dual Incremental Encoder
Option Module
Table 88 - Dual Incremental Encoder Jumper Settings
Table 89 - Dual Incremental Encoder Specifications
20-750-DENC-1
20-750-S1
20-750-DENC-1
See
Important
statement on this page.
Jumper
Enabled Position
Storage Position
P3 - Safety Jumper
Enables use with speed
monitoring safety option
(20-750-S1).
P4 - 12V Jumper
Enables use with 12 volt
supply in “Enabled”
position and 5 volt supply
in “Storage” position.
Consideration
Description
Input
Differential or Single Ended operation, Constant Current Sink operation ~10 mA
5V DC minimum to 15V DC maximum sourcing 10 mA
minimum high state voltage of 3.5V DC
maximum low state voltage of 0.4V DC
Maximum Cable Length
30 m (100 ft) @ 5V, 183 m (600 ft) @ 12V
Maximum Input Frequency
250 kHz
IMPORTANT
When used with the Safe Speed Monitor option, both modules must be
installed on the same backplane using ports 4, 5, or 6.
P3
P3
P4
P4