Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
95
Programming and Parameters
Chapter 3
A195 [Reset Meters]
Related Parameter(s):
...
Resets the marker that indicates Fault Times and Energy usage.
Options
0 “Ready/Idle” (Default)
1 “Reset MWh”
Also resets kWh marker.
2 “Reset Time”
min, hr, and x10hr
A196 [Testpoint Sel]
Related Parameter(s):
Used by Rockwell Automation field service personnel.
Values
Default:
1024
Min/Max:
1024/65535
Display:
1
A197 [Fault Clear]
Related Parameter(s):
,
Stop drive before changing this parameter.
Resets a fault and clears the fault queue. Used primarily to clear a fault over network communications.
Options
0 “Ready/Idle” (Default)
1 “Reset Fault”
2 “Clear Buffer”
Clears all fault buffers.
A198 [Program Lock]
Protects parameters against change by unauthorized personnel. Enter a user-selected password to lock the parameters via Option 1. Enter the same password to unlock the
parameters.
Options
0 “Unlocked” (Default)
1 “Locked”
Locks all parameters.
2 “Locked”
Parameter edits allowed over communications network.
3 “Locked”
Locks
[Maximum Freq] and
[Boost Select].
A199 [Motor NP Poles]
Related Parameter(s):
Sets the motor poles. This is used to calculate
[Output RPM].
Values
Default:
4
Min/Max:
2/40
Display:
1
A200 [Motor NP FLA]
Set to the motor nameplate rated full load amps.
Values
Default:
Drive Rated Amps
Min/Max:
0.1/(Drive Rated Amps × 2)
Display:
0.1 Amps
A201 [PID Invert Error]
(With FRN 6.xx and later.)
When set to “Inverted”, changes the sign of the PID error. This causes an increase in the drive output frequency with PID Feedback greater than PID Setpoint, and a decrease in drive
output frequency with PID Feedback less than PID Setpoint.
Options
0 “Not Inverted” (Default)
1 “Inverted”
Locks all parameters.