68
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 3
Programming and Parameters
T058 [Relay 1 On Time]
Sets delay time before Relay energizes after required condition testing.
Values
Default:
0.0 Secs
Min/Max:
0.0/600.0 Secs
Display:
0.1 Secs
T059 [Relay 1 Off Time]
Sets delay time before Relay de-energizes after required condition testing ceases.
Values
Default:
0.0 Secs
Min/Max:
0.0/600.0 Secs
Display:
0.1 Secs
IMPORTANT
Do not use this parameter with Auxiliary Motor Control mode AutoSwap enabled.
T060 [Relay Out2 Sel]
Sets the condition that changes the state of the output relay contacts.
Options
0 “Ready/Fault” (Default)
Relay changes state when power is applied. This indicates that the drive is ready for operation. Relay returns drive to shelf state
when power is removed or a fault occurs.
1 “At Frequency”
Drive reaches commanded frequency.
2 “MotorRunning” (Default)
Motor is receiving power from the drive.
3 “Hand Active”
Active when drive is in local control.
4 “Motor Overld”
Motor overload condition exists.
5 “Ramp Reg”
Ramp regulator is modifying the programmed accel/decel times to avoid an overcurrent or overvoltage fault from occurring.
6 “Above Freq”
• Drive exceeds the frequency (Hz) value set in
[Relay Out2 Level].
• Use T061 to set threshold.
7 “Above Cur”
• Drive exceeds the current (% Amps) value set in
[Relay Out2 Level].
• Use T061 to set threshold.
8 “Above DCVolt”
• Drive exceeds the DC bus voltage value set in
[Relay Out2 Level].
• Use T061 to set threshold.
9 “Above Anlg 2”
• Analog input voltage (I/O Terminal 17) exceeds the value set in
[Analog In 2 Sel] is set to 3 “Voltage Mode - Bipolar”.
• This parameter setting can also be used to indicate a PTC trip point when the input (I/O Terminal 17) is wired to a PTC and
external resistor.
• Use T061 to set threshold.
10 “Above PF Ang”
• Power Factor angle has exceeded the value set in
[Relay Out2 Level].
• Use T061 to set threshold.
11 “Anlg In Loss”
Analog input loss has occurred. Program
[Analog In 1 Loss] and/or
[Analog In 2 Loss] for desired action when input
loss occurs.
12 “ParamControl”
Enables the output to be controlled over network communications by writing to
[Relay Out2 Level]. (0 = Off, 1 = On.)
13 “Retries Exst”
Value set in
[Auto Rstrt Tries] is exceeded.
14 “NonRec Fault”
• Number of retries for
[Auto Rstrt Tries] is exceeded OR
• Non-resettable fault occurs OR
•
[Auto Rstrt Tries] is not enabled.
15 “Reverse”
Drive is commanded to run in reverse direction.
16 “Logic In 1”
An input is programmed as “Logic In 1” and is active.
17 “Logic In 2”
An input is programmed as “Logic In 2” and is active.
23 “Aux Motor”
Auxiliary Motor is commanded to run. Refer to Appendix C for details.
24 “Fault” (with FRN 7.xx and later) Relay remains in the off state when power is applied to the drive and energizes when a fault occurs. This is inverted from Option
0, “Ready/Fault”.
IMPORTANT
[Relay Out2 Level] must be entered in percent of drive rated output current.