Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
59
Programming and Parameters
Chapter 3
b007 [Fault 1 Code]
...
A code that represents a drive fault. [Fault 1 Code] is the most recent fault. Repetitive faults will only be recorded once.
Refer to
for fault code descriptions.
Values
Default:
Read Only
Min/Max:
0/122
Display:
1
b008 [Process Display]
32 bit parameter.
Output frequency scaled by A160 [Process Factor]
Values
Default:
Read Only
Min/Max:
0.00/9999
Display:
0.01 – 1
3
2
Output
Freq
Process
Display
Process
Factor
x
=
b010 [Output Power]
Output power present at T1, T2 & T3 (U, V & W).
Values
Default:
Read Only
Min/Max:
0.0/999.9 kW
Display:
0.1 kW
b011 [Elapsed MWh]
Accumulated output energy of the drive.
Values
Default:
Read Only
Min/Max:
0/3276.7 MWh
Display:
0.1 MWh
b012 [Elapsed Run Time]
Displays the accumulated time that the drive has output power since the last
[Reset Meter].
Time is displayed in 10 hour increments.
Values
Default:
Read Only
Min/Max:
0/9999 Hrs
Display:
1 = 10 Hrs
b013 [Torque Current]
Displays the torque portion of the output current.
Values
Default:
Read Only
Min/Max:
0.0/(Drive Rated Amps × 2)
Display:
0.1 Amps
b014 [Drive Temp]
Present operating temperature of the drive power section.
Values
Default:
Read Only
Min/Max:
0/120 degC
Display:
1 degC