118
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 4
Troubleshooting
Drive does not Start from Start or Run Inputs wired to the
terminal block.
Drive does not Start from Integral Keypad.
Cause(s)
Indication
Corrective Action
Drive is Faulted
Flashing red status light
Clear fault.
• Press Stop.
• Cycle power.
• Set
[Fault Clear] to option 1 “Clear Faults”.
• Cycle digital input if
...
[Digital Inx Sel] is set to option 7 “Clear Fault”.
Incorrect programming.
•
[Start Source] is set to option 0 “Keypad” or option 5
“RS485 (DSI) Port”.
•
[Digital Inx Sel] is set to option 5 “Local” and
the input is active.
None
Check parameter settings.
Incorrect input wiring.
See
• 2 wire control requires Run Forward, Run Reverse or Jog
input.
• 3 wire control requires Start and Stop inputs
• Stop input is always required.
None
Wire inputs correctly and/or install jumper.
Incorrect Sink/Source DIP switch setting.
None
Set switch to match wiring scheme.
Cause(s)
Indication
Corrective Action
Integral keypad is not enabled.
Green LED above Start
key is not illuminated.
• Set
[Start Source] to option 0 “Keypad”.
• Set parameter
[Digital Inx Sel] to option 5 “Local” and activate
the input.
I/O Terminal 01 “Stop” input is not present.
None
Wire inputs correctly and/or install jumper.