Other types of shielded cable are available, but the selection of these types may
limit the allowable cable length. Particularly, some of the newer cables twist 4
conductors of THHN wire and wrap them tightly with a foil shield. This
construction can greatly increase the cable charging current required and
reduce the overall drive performance. Unless specified in the individual
distance tables as tested with the drive, these cables are not recommended and
their performance against the lead length limits supplied is not known.
Reflected Wave Protection
The drive should be installed as close to the motor as possible. Installations
with long motor cables may require the addition of external devices to limit
voltage reflections at the motor (reflected wave phenomena). See
for
recommendations.
The reflected wave data applies to all frequencies 2 to 10 kHz.
For 240V ratings, reflected wave effects do not need to be considered.
Output Disconnect
The drive is intended to be commanded by control input signals that will start
and stop the motor. A device that routinely disconnects then reapplies output
power to the motor for the purpose of starting and stopping the motor should
Table 3 - Recommended Shielded Wire
Location
Rating/Type
Description
Standard
(Option 1)
600V, 90°C (194°F)
XHHW2/RHW-2
Anixter B209500-B209507,
Belden 29501-29507,
or equivalent
• Four tinned copper conductors with XLPE
insulation.
• Copper braid/aluminum foil combination shield
and tinned copper drain wire.
• PVC jacket.
Standard
(Option 2)
Tray rated 600V, 90°C
(194°F) RHH/RHW-2
Anixter OLF-7xxxxx
or equivalent
• Three tinned copper conductors with XLPE
insulation.
• 5 mil single helical copper tape (25% overlap min.)
with three bare copper grounds in contact with
shield.
• PVC jacket.
Class I & II;
Division I & II
Tray rated 600V, 90°C
(194°F) RHH/RHW-2
Anixter 7V-7xxxx-3G
or equivalent
• Three bare copper conductors with XLPE insulation
and impervious corrugated continuously welded
aluminum armor.
• Black sunlight resistant PVC jacket overall.
• Three copper grounds on #10 AWG and smaller.
Table 4 - Maximum Cable Length Recommendations
Reflected Wave
380...480V Ratings
Motor Insulation Rating
Motor Cable Only
(1)
(1) Longer cable lengths can be achieved by installing devices on the output of the drive. Consult factory for recommendations.
1000 Vp-p
7.6 meters (25 feet)
1200 Vp-p
22.9 meters (75 feet)
1600 Vp-p
152.4 meters (500 feet)