Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
43
Installation/Wiring
Chapter 1
Figure 15 - Connections and Grounding
(1) Shielded Enclosure required for 200-240V AC 11-22 kW (15-30 HP) PowerFlex 400 drives.
7.5 (10)
22C-D017N103
22-RF018-CS
10
No
11 (15)
22C-D022N103
22-RF026-CS
10
No
15 (20)
22C-D030N103
22-RFD036
100
No
18.5 (25)
22C-D038A103
22-RFD050
150
No
22 (30)
22C-D045A103
22-RFD050
150
No
30 (40)
22C-D060A103
22-RFD070
50
No
37 (50)
22C-D072A103
22-RFD100
50
No
45 (60)
22C-D088A103
22-RFD100
50
No
55 (75)
22C-D105A103
22-RFD150
150
No
75 (100)
22C-D142A103
22-RFD180
50
No
90 (125)
22C-D170A103
22-RFD208
50
No
110 (150)
22C-D208A103
22-RFD208
50
No
132 (200)
22C-D260A103
22-RFD323
50
Required
160 (250)
22C-D310A103
22-RFD480
50
Required
200 (300)
22C-D370A103
22-RFD480
50
Required
250 (350)
22C-D460A103
22-RFD480
50
Required
Table 13 - PowerFlex 400 – FCC Part 15 Subpart B Compliance
PowerFlex 400 Drive
Required Filter
Restrict Motor
Cable to (Meters)
Install Drive and
Filter in Enclosure
kW (HP)
Cat No.
R/L1
S/L2
T/L
3
U/T1
V/T2
W/T
3
EMI Fittings and Metal Conduit
IP
3
0/NEMA 1/UL Type 1
Option Kit (Frame C Drives Only)
Shielded Enclosure
(1)
Building Structure Steel
Enclosure Ground Connection
EMI Filter
L1'
L2'
L
3
'
L1
L2
L
3
Shielded Motor Cable