Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
31
Installation/Wiring
Chapter 1
Figure 11 - User Installed Auxiliary Relay Card (Frames D, E, F, G and H Only)
18
Analog Common 2
–
For Analog Input 2. Electronically isolated from digital
I/O and opto output. With Analog Input 2, provides
one fully isolated analog input channel.
19
Opto Output
At Frequency
Program with T065 [Opto Out Sel].
20
RS485 (DSI) Shield
–
Terminal connected to Safety Ground - PE when using
the RS485 (DSI) Communication Port.
(1) See Footnotes (1) and (4) on page
(2)
Important
information regarding Stop commands and the [Digital Inx Sel] Purge option is provided on page
Table 10 - Relay Terminal Designations and DIP Switches
No.
Signal
Default
Description
Param.
R1
#1 Relay N.O.
Ready/Fault
Normally open contact for No. 1 output relay.
R2
#1 Relay Common
–
Common for output relay.
R3
#1 Relay N.C.
Ready/Fault
Normally closed contact for No. 1 output relay.
R4
#2 Relay N.O.
Motor Running
Normally open contact for No. 2 output relay.
R5
#2 Relay Common
–
Common for output relay.
R6
#2 Relay N.C.
Motor Running
Normally closed contact for No. 2 output relay.
Selection DIP Switches:
Analog Input (AI1 & AI2)
Analog Output (AO1 & AO2)
0-10V
Sets analog output to either voltage or current.
Settings must match:
AI1 & T069 [Analog In 1 Sel]
AI2 & T073 [Analog In 2 Sel]
AO1 & T082 [Analog Out1 Sel]
AO2 & T085 [Analog Out2 Sel]
Sink/Source DIP Switch
Source (SRC)
Inputs can be wired as Sink (SNK) or Source (SRC)
via DIP Switch setting.
Table 9 - Control I/O Terminal Designations
No.
Signal
Default
Description
Param.
3
A
3
B 4A 4B 5A 5B
6A 6B 7A 7B
8
A
8
B