
70
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 3
Programming and Parameters
T065 [Opto Out Sel]
Determines the operation of the programmable opto output.
Options
0 “Ready/Fault”
Opto output is active when power is applied. This indicates that the drive is ready for operation. Opto output is inactive when
power is removed or a fault occurs.
1 “At Frequency” (Default)
Drive reaches commanded frequency
2 “MotorRunning”
Motor is receiving power from the drive.
3 “Hand Active”
Active when drive is in local control.
4 “Motor Overld”
Motor overload condition exists.
5 “Ramp Reg”
Ramp regulator is modifying the programmed accel/decel times to avoid an overcurrent or overvoltage fault from occurring.
6 “Above Freq”
• Drive exceeds the frequency (Hz) value set in
[Opto Out Level].
• Use T066 to set threshold.
7 “Above Cur”
• Drive exceeds the current (% Amps) value set in
[Opto Out Level].
• Use T066 to set threshold.
8 “Above DCVolt”
• Drive exceeds the DC bus voltage value set in
[Opto Out Level].
• • Use T066 to set threshold.
9 “Above Anlg 2”
• Analog input voltage (I/O Terminal 17) exceeds the value set in
[Opto Out Level].
[Analog In 2 Sel] is set to 3 “Voltage Mode - Bipolar”.
• This parameter setting can also be used to indicate a PTC trip point when the input (I/O Terminal 17) is wired to a PTC and
external resistor.
• Use T066 to set threshold.
10 “Above PF Ang”
• Power Factor angle has exceeded the value set in
[Opto Out Level].
• Use T066 to set threshold.
11 “Anlg In Loss”
Analog input loss has occurred. Program
[Analog In 1 Loss] and/or
[Analog In 2 Loss] for desired action when input
loss occurs.
12 “ParamControl”
Enables the output to be controlled over network communications by writing to
[Opto Out Level]. (0 = Off, 1 = On.)
13 “Retries Exst”
Value set in
[Auto Rstrt Tries] is exceeded.
14 “NonRec Fault”
• Number of retries for
[Auto Rstrt Tries] is exceeded, or
• Non-resettable fault occurs, or
•
[Auto Rstrt Tries] is not enabled.
15 “Reverse”
Drive is commanded to run in reverse direction.
16 “Logic In 1”
An input is programmed as “Logic In 1” and is active.
17 “Logic In 2”
An input is programmed as “Logic In 2” and is active.
24 “Fault” (with FRN 7.xx and later) Relay remains in the off state when power is applied to the drive and energizes when a fault occurs. This is inverted from Option
0, “Ready/Fault”.
IMPORTANT
Value for
[Opto Out Level] must be entered in percent of drive rated output current.
T066 [Opto Out Level]
32 bit parameter.
Determines the on/off point for the opto output when
[Opto Out Sel] is set to option 6, 7, 8, 9, 10,or 12.
.
Values
Default:
0.0
Min/Max:
0.0/9999
Display:
0.1
32
T065 Setting
T066 Min/Max
6
0/320 Hz
7
0/180%
8
0/815 Volts
9
0/100%
10
1/180 degs
12
0/1