76
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 3
Programming and Parameters
T084 [Anlg Out1 Setpt]
Sets direct parameter control over the analog output. If enabled, this sets the percent value of analog output.
Values
Default:
0.0%
Min/Max:
0.0/100.0%
Display:
0.1%
T085 [Analog Out2 Sel]
Sets the analog output signal mode (0-20 mA, 4-20 mA, or 0-10V). The output is used to provide a signal that is proportional to several drive conditions. This parameter must match
DIP Switch AO2 setting.
Values
Default:
1
Min/Max:
0/29
Display:
1
Setting
Output Range
Minimum Output Value
Maximum Output Value =
[Analog Output High]
Filter
(1)
(1) For settings with the filter enabled, if a 0-100% step change occurs, the output will reach 95% in 500 milliseconds, 99% in 810 milliseconds and 100% in 910 milliseconds.
DIP Switch
AO2 Setting
Related
Parameter
0 OutFreq 0-10
0-10V
0V = 0 Hz
[Maximum Freq]
None
10V
1 OutCurr 0-10
0-10V
0V = 0 Amps
200% Drive Rated FLA
Filter A
10V
2 OutTorq 0-10
0-10V
0V = 0 Amps
200% Drive Rated FLA
Filter A
10V
3 OutVolt 0-10
0-10V
0V = 0 Volts
120% Drive Rated Output V
None
10V
4 OutPowr 0-10
0-10V
0V = 0 kW
200% Drive Rated Power
Filter A
10V
5 Setpnt 0-10
0-10V
0V = 0.0%
100.0% Setting
None
10V
6 TstData 0-10
0-10V
0V = 0000
65535 (Hex FFFF)
None
10V
7 OutFreq 0-20
0-20 mA
0 mA = 0 Hz
[Maximum Freq]
None
20 mA
8 OutCurr 0-20
0-20 mA
0 mA = 0 Amps
200% Drive Rated FLA
Filter A
20 mA
9 OutTorq 0-20
0-20 mA
0 mA = 0 Amps
200% Drive Rated FLA
Filter A
20 mA
10 OutVolt 0-20
0-20 mA
0 mA = 0 Volts
120% Drive Rated Output V
None
20 mA
11 OutPowr 0-20
0-20 mA
0 mA = 0 kW
200% Drive Rated Power
Filter A
20 mA
12 Setpnt 0-20
0-20 mA
0 mA = 0.0%
100.0% Setting
None
20 mA
13 TstData 0-20
0-20 mA
0 mA = 0000
65535 (Hex FFFF)
None
20 mA
14 OutFreq 4-20
4-20 mA
4 mA = 0 Hz
[Maximum Freq]
None
20 mA
15 OutCurr 4-20
4-20 mA
4 mA = 0 Amps
200% Drive Rated FLA
Filter A
20 mA
16 OutTorq 4-20
4-20 mA
4 mA = 0 Amps
200% Drive Rated FLA
Filter A
20 mA
17 OutVolt 4-20
4-20 mA
4 mA = 0 Volts
120% Drive Rated Output V
None
20 mA
18 OutPowr 4-20
4-20 mA
4 mA = 0 kW
200% Drive Rated Power
Filter A
20 mA
19 Setpnt 4-20
4-20 mA
4 mA = 0.0%
100.0% Setting
None
20 mA
20 TstData 4-20
4-20 mA
4 mA = 0000
65535 (Hex FFFF)
None
20 mA
21 MinFreq 0-10
0-10V
0V = Min. Freq
[Maximum Freq]
None
10V
22 MinFreq 0-20
0-20 mA
0 mA = Min. Freq
[Maximum Freq]
None
20 mA
23 MinFreq 4-20
4-20 mA
4 mA = Min. Freq
[Maximum Freq]
None
20 mA
24 AnlgIn1 0-10
0-10V
0V = 0.0%
100.0% Setting
Filter A
10V
25 AnlgIn1 0-20
0-20 mA
0 mA = 0.0%
100.0% Setting
Filter A
20 mA
26 AnlgIn1 4-20
4-20 mA
4 mA = 0.0%
100.0% Setting
Filter A
20 mA
27 AnlgIn2 0-10
0-10V
0V = 0.0%
100.0% Setting
Filter A
10V
28 AnlgIn2 0-20
0-20 mA
0 mA = 0.0%
100.0% Setting
Filter A
20 mA
29 AnlgIn2 4-20
4-20 mA
4 mA = 0.0%
100.0% Setting
Filter A
20 mA