Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
69
Programming and Parameters
Chapter 3
T061 [Relay Out2 Level]
32 bit parameter.
Sets the trip point for the digital output relay if the value of T060 [Relay Out2 Sel] is 6, 7, 8, 9, 10 or 12
.
Values
Default:
0.0
Min/Max:
0.0/9999
Display:
0.1
3
2
T060 Setting
T061 Min/Max
6
0/320 Hz
7
0/180%
8
0/815 Volts
9
0/100%
10
1/180 degs
12
0/1
T063 [Relay 2 On Time]
Sets delay time before Relay energizes after required condition testing.
Values
Default:
0.0 Secs
Min/Max:
0.0/600.0 Secs
Display:
0.1 Secs
T064 [Relay 2 Off Time]
Sets delay time before Relay de-energizes after required condition testing ceases.
Values
Default:
0.0 Secs
Min/Max:
0.0/600.0 Secs
Display:
0.1 Secs
IMPORTANT
Do not use this parameter with Auxiliary Motor Control mode AutoSwap enabled.