C-28
EtherNet/IP Objects
Class Code
Products such as PowerFlex drives use this object for faults. Adapters
use this object for events.
Instances
The number of instances depends on the maximum number of faults or
events supported in the queue. The maximum number of faults/events
can be read in Instance 0, Attribute 2.
Class Attributes
DPI Fault Object
Hexadecimal
Decimal
0x97
151
Instances (Dec.) Single-Drive Mode
Multi-Drive Mode
0 – 16383
Instances 0 – 16383 in the drive
Instances 0 – 16383 in Drive 0
16384 – 17407
Instances 0 – 1023 in the adapter
Instances 0 – 1023 in the adapter
17408 – 18431
Instances 0 – 1023 in the adapter
Instances 0 – 1023 in Drive 1
18432 – 19455
Instances 0 – 1023 in the slave
Instances 0 – 1023 in Drive 2
19456 – 20479
Not supported
Instances 0 – 1023 in Drive 3
20480 – 21503
Not supported
Instances 0 – 1023 in Drive 4
21504 – 22527
Not supported
Instances 0 – 1023 in the adapter
Attribute
ID
Access
Rule
Name
Data Type
Description
1
Get
Class Revision
WORD
Revision of object
2
Get
Number of
Instances
WORD
Maximum number of faults/events that the
device can record in its queue
3
Set
Fault Command
Write
BYTE
0 = No Operation
1 = Clear Fault/Event
2 = Clear Fault/Event Queue
3 = Reset Device
4
Get
Fault Trip
Instance Read
WORD
Fault that tripped the device. For adapters,
this value is always 1 when faulted.
5
Get
Fault Data List
STRUCT of:
BYTE
BYTE
WORD[n]
Reserved
6
Get
Number of
Recorded Faults
WORD
Number of faults/events in the queue. A
“0” indicates the fault queue is empty.
7
Get
Fault Parameter
Reference
WORD
Reserved
Summary of Contents for 22-COMM-E FRN 1.xxx
Page 1: ...EtherNet IP Adapter 22 COMM E FRN 1 xxx User Manual...
Page 4: ...S ii Summary of Changes...
Page 8: ...iv Table of Contents...
Page 12: ...P 4 About This Manual Notes...
Page 44: ...4 8 Configuring the Scanner or Bridge Notes...
Page 60: ...6 10 Using Explicit Messaging Notes...
Page 112: ...B 6 Adapter Parameters Notes...
Page 148: ...C 36 EtherNet IP Objects Notes...
Page 164: ...I 6 Index...
Page 165: ......