Configuring the Scanner or Bridge
4-5
The Module Properties dialog box (
Figure 4.8
) appears.
Figure 4.8 Module Properties Dialog Box - Page 1
3.
Edit the following information about the adapter:
4.
Under Connection Parameters, edit the following:
Type the number of bytes that are required for your I/O in the Input
Size and Output Size boxes. The size will depend on the I/O that you
enabled in the adapter. This information can be found in
Parameter
22 - [DSI I/O Cfg]
in the adapter.
Table 4.A
shows common
configuration Input/Output sizes.
In our example, we typed 4 in the Input Size and Output Size boxes
because the Operating Mode Switch on the adapter is set to “Single”
(default) and
Parameter 22 - [DSI I/O Cfg]
is set to “Drive 0” (only
one drive being connected). Logic Command/Reference uses 2
Box
Type
Name
A name to identify the adapter and drive.
Comm. Format
Data - INT
.
This setting formats the data in 16-bit words.
IP Address
The IP address of the adapter.
Box
Assembly Instance Size
Input
1
(This value is
required.)
The value will vary based on your application
(setting of
Parameter 22 - [DSI I/O Cfg]
). It
will contain 2 additional words for ENBT
overhead. Refer to
Table 4.A
on
page 4-6
.
Output
2
(This value is
required.)
The value will vary based on your application
(setting of
Parameter 22 - [DSI I/O Cfg]
).
Refer to
Table 4.A
on
page 4-6
.
Configuration
6
(This value is
required.)
0 (
This value is required.)
Summary of Contents for 22-COMM-E FRN 1.xxx
Page 1: ...EtherNet IP Adapter 22 COMM E FRN 1 xxx User Manual...
Page 4: ...S ii Summary of Changes...
Page 8: ...iv Table of Contents...
Page 12: ...P 4 About This Manual Notes...
Page 44: ...4 8 Configuring the Scanner or Bridge Notes...
Page 60: ...6 10 Using Explicit Messaging Notes...
Page 112: ...B 6 Adapter Parameters Notes...
Page 148: ...C 36 EtherNet IP Objects Notes...
Page 164: ...I 6 Index...
Page 165: ......