Viewing the Adapter’s Web Pages
9-11
2.
Click
Save changes
.
Important:
It is recommended that
Parameter 30 - [Web
Features]
Proc Dsp Cfg Bit 1 value be set to “0”
(Disabled) after configuration. Otherwise the
configuration can be changed anytime the web page is
accessed with a browser.
DSI device information pages show a device’s module information,
diagnostic information, and fault queue.
Figure 9.8
shows a module
information example page for the Port 0 device (host).
Figure 9.9
and
Figure 9.10
respectively show diagnostic information and fault queue
example pages for the Port 5 device (22-COMM-E adapter).
Figure 9.8 Example of Port 0 (PowerFlex 40 Drive) Module Information Page
DSI Device Information Pages
Information
Description
Product text
Text identifying the device
Vendor ID
1 = Allen-Bradley
Device type
127
Product code
Code for the product name and its rating
Revision
Firmware revision used by the device
Serial number
Serial number of the device
Status
Operating status of the device (for example, faulted)