49
Scholar V Installation & Startup Manual 07/2016 New
APPENDIX G - INSTALLATION OF ELECTRIC HEATERS ON ALL VAIVA MODELS
1.01 TOOLS/FIELD FURNISHED SUPPLIES
WARNING
BEFORE INSTALLING, SERVICING OR MAINTAINING THIS EQUIPMENT, SWITCH THE
ELECTRIC POWER TO “OFF” AT THE DISCONNECT.
FAILURE TO DO THIS COULD RESULT IN PROPERTY DAMAGE, BODILY INJURY OR
DEATH.
• Power Drill/Driver and Extension
• T5 TORX Bits
• Needle Nose Pliers
• Wire Stripper/Cutter
• Screwdriver with Slotted Bit
1.02 INSPECTION/UNPACKING/HANDLING
Electric heaters are shipped inside the Scholar V unit in the lower left side. Use care
when handing the heaters. The heaters are wrapped in brown paper for protection
during transit. Remove the paper before installing the heaters. The heater’s elements
are fragile and can break and the support frames can bend when handled improperly.
Make sure that the heater’s elements are not touching the frame.
1.03 MOUNTING THE ELECTRIC HEATERS
The heaters are installed on top of the heat pump over the supply air blower’s
discharge. Marvair recommends that the plenum be installed prior to installing the
heaters to minimize the chance of damaging the heaters when installing the plenum.
A. Remove the front panel of the plenum. A rectangular opening with two screws holes
is visible.