Scholar V Installation & Startup Manual 07/2016 New
12
Heating Set-Point (auto)
This set point is automatically calculated and is not directly adjustable by the end
user. Adjustment is made by changing the Auto Cool/Heat Differential (see below).
Humidity Set-Point
This is the user adjustable relative humidity the unit runs to try to achieve in the
Cooling Mode or in the Dehumidification with Reheat mode. The Dehumidification
with Reheat mode will automatically come on if the temperature is satisfied in cooling
but the relative humidity is still high. Cooling is forced on for dehumidification with
hot gas reheat to keep from overcooling the space.
Auto Cool/Heat Differential
This number is subtracted from the Cooling Set Point to establish the Heating Set
Point while the unit is in the Auto Cool/Heat Mode.
Low Ambient Override
This is the outside temperature at which heat pump heating operation is
discontinued and resistance heating is used. It is Password Protected
D. Other Screens
There are several other screens used for diagnostics. The screens are shown below
but detailed discussion is not provided in this document.