Standard Flushing Bypass Kit
Comprises:
● Shut off valves
Regulating Flushing Bypass Kit
Comprises:
● Shut off valves
●
Double regulating valve
Factory fitted to protect the evaporator from clogging by sediment and to enable the water system
to be purged before running.
Single Pump + Flushing Bypass
Comprises:
●
Single pump with valve isolation
● Shut off valves
●
Filters
Single Pump + Regulating Bypass
Comprises:
●
Single pump with valve isolation
● Shut off valves
●
Filters
●
Double regulating valves
Run & Standby Pumps + Flushing Bypass
Comprises:
●
Run and standby pumps with valve isolation
● Shut off valves
●
Filters
●
Non return valves
Run & Standby Pumps + Regulating Bypass
Comprises:
●
Run and standby pumps with valve isolation
● Shut off valves
●
Filters
●
Double regulating valves
●
Non return valves
Pump Options
The pumps can be offered with two options for external static pressure: standard or larger head pressure to overcome
systems with a higher pressure drop. The factory fitted run/standby pumps have a shut of valve to the inlet and a non-
return valve to the outlet, which enables one pump to be maintained without interrupting the chiller flow. Run/standby
pumps are rotated automatically to ensure even pump usage and prolong component life. Electrical switchgear and
isolating valves are supplied as standard.
Pump - AC Motor - Fixed Speed
A factory fitted in line single or run/standby pump package is available in a standard or larger external head; please
specify at order. Flow can be proved via the microprocessor display. Factory fitted and supplied as standard complete
with:
● Differential pressure sensor
●
Isolating valves
●
Inlet strainer
●
Electrical switch gear
Pump - Inverter Driven - Variable Speed
A factory fitted in line single or run/standby pump is available in a standard or larger external head; please specify at
order.
Flow is varied via an electronic flow meter, depending on system requirements. Adjustment and monitoring is via the
microprocessor display. Factory fitted and supplied as standard complete with:
● Differential pressure sensor
●
Isolating valves
●
Inlet strainer
●
Electrical switch gear
●
Inverter panel with ventilation fan and panel heater (High/Low ambient operation)