Technical Data
Ecodesign - DCF (RQ)
Notes Units
DCF064DR-12MYV0
DCF068TR-1
1RNXX
DCF070TR-12RXXX
DCF055DR-13MXY0
SEPR
1, 3, 5
6.26
5.83
6.17
6.43
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
701698.64
795369.98
771185.32
583456.74
Rated Refrigerant Capacity P
A
1, 3, 5
kW
592.50
626.20
642.00
506.40
Rated Power Input D
A
kW
196.19
217.43
216.89
157.27
Rated EER
DC,A
3.02
2.88
2.96
3.22
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
650.9 / 542.1
615.9 / 540.3
630.2 / 554.7
555.8 / 454.4
Declared Power Input D
B
kW
160.5 / 129.8
156.8 / 135.3
155.5 / 134.0
128.7 / 102.5
Declared EER
DC,B
4.06 / 4.18
3.93 / 3.99
4.05 / 4.14
4.32 / 4.43
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
584.3 / 474.3
584.9 / 500.1
602.0 / 520.0
491.6 / 405.9
Declared Power Input D
C
kW
107.6 / 84.8
112.1 / 96.0
111.3 / 93.4
85.2 / 69.0
Declared EER
DC,C
5.43 / 5.59
5.22 / 5.21
5.41 / 5.57
5.77 / 5.89
Declared Refrigerant Capacity
P
D
kW
473.3 / 365.4
500.2 / 434.0
512.9 / 454.5
404.5 / 301.1
Declared Power Input D
D
kW
55.4 / 54.3
64.2 / 68.7
61.3 / 66.1
48.2 / 43.7
Declared EER
DC,D
8.54 / 6.73
7.79 / 6.31
8.37 / 6.87
8.40 / 6.89
SSCEE
2, 3, 5
%
171
159
169
177
SSCEE Tier
Tier 1 (2018)
Not Compliant
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
593.20
627.00
642.80
507.10
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
592.50
626.20
642.00
506.40
Declared EER
d
35°C
3.02
2.88
2.96
3.22
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
650.9 / 542.1
615.9 / 540.3
630.2 / 554.7
555.8 / 454.4
Declared EER
d
30°C
4.06 / 4.18
3.93 / 3.99
4.05 / 4.14
4.32 / 4.43
Declared Cooling Capacity
25°C Pdc
kW
584.3 / 474.3
584.9 / 500.1
602.0 / 520.0
491.6 / 405.9
Declared EER
d
25°C
5.43 / 5.59
5.22 / 5.21
5.41 / 5.57
5.77 / 5.89
Declared Cooling Capacity
20°C Pdc
kW
473.3 / 365.4
500.2 / 434.0
512.9 / 454.5
404.5 / 301.1
Declared EER
d
20°C
8.54 / 6.73
7.79 / 6.31
8.37 / 6.87
8.40 / 6.89
Sound Power Level L
dB(A)
89.97
91.27
91.13
87.34
Air fl ow rate
m³/h
255543.66
234248.35
255543.66
276838.96
Off mode P
OFF
0.14
0.15
0.15
0.14
Thermostat-off mode P
TO
3.87
4.30
4.08
3.49
Standby Mode P
SB
0.27
0.30
0.32
0.28
Crankcase heater mode P
CK
0.00
0.00
0.00
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Technical Data
Ecodesign - DCF (RQ)
Notes Units
DCF062DR-14MYY0
DCF065DR-14MYV0
DCF069TR-14RNXX
DCF077TR-13RXXY
SEPR
1, 3, 5
6.40
6.37
6.15
6.19
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
663605.89
696250.28
771151.67
852517.84
Rated Refrigerant Capacity P
A
1, 3, 5
kW
572.90
598.50
639.70
711.80
Rated Power Input D
A
kW
179.03
190.61
207.69
240.47
Rated EER
DC,A
3.20
3.14
3.08
2.96
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
628.4 / 526.4
656.6 / 546.5
625.8 / 548.6
684.3 / 607.7
Declared Power Input D
B
kW
147.1 / 120.7
155.7 / 126.2
149.1 / 128.8
168.4 / 146.8
Declared EER
DC,B
4.27 / 4.36
4.22 / 4.33
4.20 / 4.26
4.06 / 4.14
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
568.7 / 458.4
588.5 / 477.1
592.6 / 506.6
658.8 / 575.8
Declared Power Input D
C
kW
100.3 / 78.4
104.7 / 82.8
106.6 / 91.2
121.9 / 103.9
Declared EER
DC,C
5.67 / 5.84
5.62 / 5.77
5.56 / 5.56
5.40 / 5.54
Declared Refrigerant Capacity
P
D
kW
457.7 / 354.6
478.1 / 365.3
511.0 / 436.2
568.6 / 486.3
Declared Power Input D
D
kW
54.3 / 51.7
56.4 / 53.7
63.4 / 65.8
67.0 / 70.8
Declared EER
DC,D
8.42 / 6.85
8.48 / 6.80
8.06 / 6.63
8.48 / 6.87
SSCEE
2, 3, 5
%
179
176
169
167
SSCEE Tier
Tier 2 (2021)
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
573.60
599.20
640.50
712.60
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
572.90
598.50
639.70
711.80
Declared EER
d
35°C
3.20
3.14
3.08
2.96
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
628.4 / 526.4
656.6 / 546.5
625.8 / 548.6
684.3 / 607.7
Declared EER
d
30°C
4.27 / 4.36
4.22 / 4.33
4.20 / 4.26
4.06 / 4.14
Declared Cooling Capacity
25°C Pdc
kW
568.7 / 458.4
588.5 / 477.1
592.6 / 506.6
658.8 / 575.8
Declared EER
d
25°C
5.67 / 5.84
5.62 / 5.77
5.56 / 5.56
5.40 / 5.54
Declared Cooling Capacity
20°C Pdc
kW
457.7 / 354.6
478.1 / 365.3
511.0 / 436.2
568.6 / 486.3
Declared EER
d
20°C
8.42 / 6.85
8.48 / 6.80
8.06 / 6.63
8.48 / 6.87
Sound Power Level L
dB(A)
87.74
88.96
90.06
91.51
Air fl ow rate
m³/h
298134.27
298134.27
298134.27
276838.96
Off mode P
OFF
0.14
0.14
0.15
0.15
Thermostat-off mode P
TO
3.26
3.71
4.21
4.66
Standby Mode P
SB
0.28
0.28
0.32
0.32
Crankcase heater mode P
CK
0.00
0.00
0.00
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od
esi
gn
136
Chillers
DeltaChill
TM
DeltaChill Technical Manual 9758541 V1.1_06_2020