Technical Data
Ecodesign - DCC (XQ)
Notes Units
DCC084TX-21SYYY
DCC087TX-21SYVV
DCC088TX-21SVVV
SEPR
1, 3, 5
6.02
5.86
5.78
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
1036048.78
1095971.42
1132969.90
Rated Refrigerant Capacity P
A
1, 3, 5
kW
842.00
866.90
884.10
Rated Power Input D
A
kW
259.08
277.85
287.98
Rated EER
DC,A
3.25
3.12
3.07
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
828.4 / 728.0
852.1 / 747.3
871.4 / 766.7
Declared Power Input D
B
kW
186.8 / 161.5
197.8 / 169.7
205.3 / 177.2
Declared EER
DC,B
4.43 / 4.51
4.31 / 4.40
4.25 / 4.33
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
786.0 / 677.1
801.9 / 694.3
821.1 / 706.8
Declared Power Input D
C
kW
133.7 / 112.6
139.7 / 118.7
145.5 / 122.3
Declared EER
DC,C
5.88 / 6.01
5.74 / 5.85
5.64 / 5.78
Declared Refrigerant Capacity
P
D
kW
693.6 / 577.9
709.4 / 589.1
721.5 / 601.2
Declared Power Input D
D
kW
99.6 / 83.2
104.8 / 86.9
107.8 / 89.9
Declared EER
DC,D
6.96 / 6.95
6.77 / 6.78
6.69 / 6.69
SSCEE
2, 3, 5
%
187
186
184
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
842.60
867.40
884.70
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
842.00
866.90
884.10
Declared EER
d
35°C
3.25
3.12
3.07
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
828.4 / 728.0
852.1 / 747.3
871.4 / 766.7
Declared EER
d
30°C
4.43 / 4.51
4.31 / 4.40
4.25 / 4.33
Declared Cooling Capacity
25°C Pdc
kW
786.0 / 677.1
801.9 / 694.3
821.1 / 706.8
Declared EER
d
25°C
5.88 / 6.01
5.74 / 5.85
5.64 / 5.78
Declared Cooling Capacity
20°C Pdc
kW
693.6 / 577.9
709.4 / 589.1
721.5 / 601.2
Declared EER
d
20°C
6.96 / 6.95
6.77 / 6.78
6.69 / 6.69
Sound Power Level L
dB(A)
88.17
89.46
89.99
Air fl ow rate
m³/h
336298.86
336298.86
336298.86
Off mode P
OFF
0.149
0.149
0.149
Thermostat-off mode P
TO
2.658
2.106
2.192
Standby Mode P
SB
0.364
0.364
0.364
Crankcase heater mode P
CK
0.00
0.00
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od
esi
gn
129
Chillers
DeltaChill
TM
DeltaChill Technical Manual 9758541 V1.1_06_2020