Fre
eC
oo
l
67
DeltaChill Technical Manual 9758541 V1.1_06_2020
Chillers
DeltaChill
TM
Technical Data
DCF Extra Quiet
Mechanical Data
Notes Units
DCF096TX-
18R
VVV
DCF099TX- 18R
VVW
DCF101TX- 18R
VWW
DCF104TX- 18R
WWW
DCF078TX-
19RXXY
DCF084TX-
20RXYY
Capacity
Number of Refrigeration Circuits
3
3
3
3
3
3
Cooling Duty - EC Fans
(1)
kW
956.0
985.1
1014.4
1043.7
780.1
844.7
Nominal Input - Mechanical
kW
311.0
326.7
342.3
358.0
220.8
243.0
EER
(2)
3.07
3.02
2.96
2.92
3.53
3.48
ESEER (Gross)
4.64
4.61
4.59
4.55
4.91
4.84
ESEER (Net)
4.29
4.25
4.22
4.17
4.54
4.45
Nominal Output - Free Cooling
kW
639.02
642.08
644.81
647.25
633.41
672.73
Ambient temperature for 100% Free Cooling (5)
°C
-3.00
-3.50
-4.00
-4.40
0.20
-0.10
Capacity Steps
%
12-24-36-48-
59-70-80-90-
100
12-24-37-48-
58-70-80-90-
100
11-24-37-47-59-
71-80-90-100
12-25-37-48-
59-71-80-90-
100
11-21-35-45-55-
69-78-88-100
10-22-35-44-
57-69-78-89-
100
Minimum Turndown Ratio
0.12
0.12
0.11
0.12
0.11
0.10
Dimensions (HxW)
mm
2682x2200
Length
mm
10506
10506
10506
10506
11638
11638
Machine Weight
(3)
kg
9480
9535
9590
9645
9785
9930
Operating Weight
kg
10200
10255
10310
10365
10590
10735
Evaporator
Shell and Tube
Water Volume (Total Internal)
l
492.5
492.5
492.5
492.5
523.0
523.0
Maximum Waterfl ow
l/s
85.9
85.9
85.9
85.9
65.0
65.0
Minimum Waterfl ow
l/s
19.9
19.9
19.9
19.9
14.9
14.9
Condenser
Face Area (Total)
m²
42.75
42.75
42.75
42.75
45.13
47.50
Nominal Airfl ow
m³/s
71.96
71.96
71.96
71.96
75.95
79.95
Condenser Fan & Motor
Quantity
18
18
18
18
19
20
Diameter
mm
800
800
800
800
800
800
Maximum Speed
rpm
725
725
725
725
725
725
Compressor
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Quantity of Compressors
9
9
9
9
9
9
Oil Charge Volume (Total)
l
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
Oil Type
Polyvinyl Ether
Refrigeration
GWP Equivalent CO
2
Tonnes
tCO
2
78.30
78.30
78.30
78.30
72.23
74.93
Charge (Total)
kg
35 + 40 + 41
35 + 40 + 41
35 + 40 + 41
35 + 40 + 41
31 + 35 + 41
31 + 39 + 41
Maximum Allowable Pressure High Side (PS)
barg
40.2
40.2
40.2
40.2
40.2
40.2
Maximum Allowable Pressure Low Side (PS)
barg
25.9
25.9
25.9
25.9
25.9
25.9
Connections
Water Inlet / Outlet - Unit
DN150
DN150
DN150
DN150
DN150
DN150
Water System
Minimum System Water Volume
(4)
l
2103.71
2103.66
2103.66
2330.37
1510.51
1510.51
Nominal Water Flow
l/s
48.25
49.71
51.19
52.67
39.37
42.63
Pressure drop
kPa
111.37
117.38
123.59
129.95
104.97
117.91
Electrical Data
Nominal Run Amps
(6)
A
586.9
607.4
628.0
648.6
449.8
491.3
Maximum Start Amps
A
853
866
887
876
722
764
Recommended Mains Fuse Size
A
630
630
670
670
500
560
Recommended Permanent Fuse Size
A
16
16
16
16
16
16
Maximum Permanent Incoming Cable Size
mm²
4
4
4
4
4
4
Evaporator Heater Rating
W
250
250
250
250
250
250
Condenser Fan - Per Fan (EC)
Full Load Amps
A
3.9
3.9
3.9
3.9
3.9
3.9
Motor Rating
kW
2.56
2.56
2.56
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
60.4 / 60.4 /
60.4
60.4 / 60.4 /
67.3
60.4 / 67.3 /
67.3
67.3 / 67.3 /
67.3
40.7 / 40.7 /
53.7
40.7 / 53.7 /
53.7
Quantity
(7)
3
3
3
3
3
3
Motor Rating
kW
36.5 / 36.5 /
36.5
36.5 / 36.5 /
41.3
36.5 / 41.3 /
41.3
41.3 / 41.3 /
41.3
25.9 / 25.9 /
33.6
25.9 / 33.6 /
33.6
Start Amps
(8)
A
326 / 326 / 326 326 / 326 / 295 326 / 295 / 295 295 / 295 / 295 210 / 210 / 326 210 / 326 / 326
(1)
Based on FC units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% ethylene glycol. All performance data is supplied in
accordance with BS EN 14511-1:2018.
(2)
EER = DX Cooling Output / (Compressor input power + Fan Input Power).
(3)
Based on standard unit without options, operating weight includes refrigerant charge and water volume. For unit weights with waterside options fi tted
please refer to Airedale.
(4)
For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations.
(5)
Ambient temperature that full Freecool capacity can be achieved.
(6)
EC fans and no pumps.
(7)
Data quoted at design fl ow-rate, 7°C supply temperature and 35°C ambient, 100% water.
(8)
Starting amps refers to the direct on line connections.
Pump electrical data is available from Airedale upon request.
Technical Data
DCF Extra Quiet
Mechanical Data
Notes Units
DCF091TX-
21R
YYY
DCF096TX-
21R
YVV
DCF098TX-
21R
VVV
DCF101TX- 21R
VVW
DCF104TX- 21R
VWW
DCF108TX- 21R
WWW
Capacity
Number of Refrigeration Circuits
3
3
3
3
3
3
Cooling Duty - EC Fans
(1)
kW
914.9
959.8
982.6
1013.4
1044.3
1075.1
Nominal Input - Mechanical
kW
265.9
287.8
298.8
313.2
327.6
342.1
EER
(2)
3.44
3.34
3.29
3.24
3.19
3.14
ESEER (Gross)
4.68
4.73
4.75
4.73
4.71
4.68
ESEER (Net)
4.36
4.35
4.40
4.37
4.34
4.29
Nominal Output - Free Cooling
kW
712.94
722.30
726.54
731.78
736.47
740.68
Ambient temperature for 100% Free Cooling (5)
°C
-0.50
-1.00
-1.30
-1.70
-2.10
-2.50
Capacity Steps
%
12-23-35-46-
58-69-79-90-
100
11-23-35-46-58-
69-79-90-100
12-24-36-47-
58-70-80-90-
100
11-23-36-47-58-
70-80-89-100
11-24-36-47-58-
70-79-90-100
12-24-36-47-
59-70-80-90-
100
Minimum Turndown Ratio
0.12
0.11
0.12
0.11
0.11
0.12
Dimensions (HxW)
mm
2682x2200
Length
mm
12770
12770
12770
12770
12770
12770
Machine Weight
(3)
kg
10475
10470
10490
10545
10600
10655
Operating Weight
kg
11380
11375
11400
11455
11510
11565
Evaporator
Shell and Tube
Water Volume (Total Internal)
l
508.0
508.0
492.5
492.5
492.5
492.5
Maximum Waterfl ow
l/s
85.9
65.0
85.9
85.9
85.9
85.9
Minimum Waterfl ow
l/s
19.9
14.9
19.9
19.9
19.9
19.9
Condenser
Face Area (Total)
m²
49.88
49.88
49.88
49.88
49.88
49.88
Nominal Airfl ow
m³/s
83.95
83.95
83.95
83.95
83.95
83.95
Condenser Fan & Motor
Quantity
21
21
21
21
21
21
Diameter
mm
800
800
800
800
800
800
Maximum Speed
rpm
725
725
725
725
725
725
Compressor
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Quantity of Compressors
9
9
9
9
9
9
Oil Charge Volume (Total)
l
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
Oil Type
Polyvinyl Ether
Refrigeration
GWP Equivalent CO
2
Tonnes
tCO
2
82.35
82.35
85.05
85.05
85.05
85.05
Charge (Total)
kg
37 + 41 + 44
37 + 41 + 44
39 + 42 + 45
39 + 42 + 45
39 + 42 + 45
39 + 42 + 45
Maximum Allowable Pressure High Side (PS)
barg
40.2
40.2
40.2
40.2
40.2
40.2
Maximum Allowable Pressure Low Side (PS)
barg
25.9
25.9
25.9
25.9
25.9
25.9
Connections
Water Inlet / Outlet - Unit
DN150
DN150
DN150
DN150
DN150
DN150
Water System
Minimum System Water Volume
(4)
l
1945.87
1964.36
2115.92
2115.92
2115.92
2344.91
Nominal Water Flow
l/s
46.17
48.44
49.59
51.14
52.70
54.26
Pressure drop
kPa
102.85
125.23
108.03
114.09
120.31
126.69
Electrical Data
Nominal Run Amps
(6)
A
532.9
573.5
594.1
614.6
635.2
655.8
Maximum Start Amps
A
805
839
860
873
894
884
Recommended Mains Fuse Size
A
560
630
630
670
670
710
Recommended Permanent Fuse Size
A
16
16
16
16
16
16
Maximum Permanent Incoming Cable Size
mm²
4
4
4
4
4
4
Evaporator Heater Rating
W
250
250
250
250
250
250
Condenser Fan - Per Fan (EC)
Full Load Amps
A
3.9
3.9
3.9
3.9
3.9
3.9
Motor Rating
kW
2.56
2.56
2.56
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
53.7 / 53.7 /
53.7
53.7 / 60.4 /
60.4
60.4 / 60.4 /
60.4
60.4 / 60.4 /
67.3
60.4 / 67.3 /
67.3
67.3 / 67.3 /
67.3
Quantity
(7)
3
3
3
3
3
3
Motor Rating
kW
33.6 / 33.6 /
33.6
33.6 / 36.5 /
36.5
36.5 / 36.5 /
36.5
36.5 / 36.5 /
41.3
36.5 / 41.3 /
41.3
41.3 / 41.3 /
41.3
Start Amps
(8)
A
326 / 326 / 326 326 / 326 / 326 326 / 326 / 326 326 / 326 / 295 326 / 295 / 295 295 / 295 / 295
(1)
Based on FC units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% ethylene glycol. All performance data is supplied in
accordance with BS EN 14511-1:2018.
(2)
EER = DX Cooling Output / (Compressor input power + Fan Input Power).
(3)
Based on standard unit without options, operating weight includes refrigerant charge and water volume. For unit weights with waterside options fi tted
please refer to Airedale.
(4)
For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations.
(5)
Ambient temperature that full Freecool capacity can be achieved.
(6)
EC fans and no pumps.
(7)
Data quoted at design fl ow-rate, 7°C supply temperature and 35°C ambient, 100% water.
(8)
Starting amps refers to the direct on line connections.
Pump electrical data is available from Airedale upon request.