Technical Data
Ecodesign - DCC (RQ)
Notes Units
DCC089TR-18SVVV
DCC094TR-18SVVW
DCC097TR-18SVWW
DCC100TR-18SWWW
SEPR
1, 3, 5
5.66
5.74
5.73
5.71
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
1163380.36
1206914.93
1248941.61
1293279.72
Rated Refrigerant Capacity P
A
1, 3, 5
kW
889.10
934.60
966.00
997.40
Rated Power Input D
A
kW
297.36
311.53
325.25
339.25
Rated EER
DC,A
2.99
3.00
2.97
2.94
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
868.6 / 763.2
908.1 / 801.1
943.2 / 825.6
978.3 / 860.7
Declared Power Input D
B
kW
211.4 / 182.0
219.6 / 190.0
231.2 / 197.2
242.8 / 208.8
Declared EER
DC,B
4.11 / 4.19
4.14 / 4.22
4.08 / 4.19
4.03 / 4.12
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
816.5 / 703.4
861.4 / 746.4
890.9 / 775.8
932.5 / 805.2
Declared Power Input D
C
kW
149.0 / 125.0
156.0 / 131.7
161.9 / 137.6
171.6 / 143.5
Declared EER
DC,C
5.48 / 5.63
5.52 / 5.67
5.50 / 5.64
5.43 / 5.61
Declared Refrigerant Capacity
P
D
kW
721.5 / 601.2
770.7 / 630.9
804.6 / 664.7
838.4 / 698.6
Declared Power Input D
D
kW
108.5 / 90.4
113.4 / 92.9
117.7 / 97.2
122.0 / 101.6
Declared EER
DC,D
6.65 / 6.65
6.80 / 6.79
6.84 / 6.84
6.87 / 6.88
SSCEE
2, 3, 5
%
179
180
178
176
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
889.60
935.20
966.60
998.00
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
889.10
934.60
966.00
997.40
Declared EER
d
35°C
2.99
3.00
2.97
2.94
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
868.6 / 763.2
908.1 / 801.1
943.2 / 825.6
978.3 / 860.7
Declared EER
d
30°C
4.11 / 4.19
4.14 / 4.22
4.08 / 4.19
4.03 / 4.12
Declared Cooling Capacity
25°C Pdc
kW
816.5 / 703.4
861.4 / 746.4
890.9 / 775.8
932.5 / 805.2
Declared EER
d
25°C
5.48 / 5.63
5.52 / 5.67
5.50 / 5.64
5.43 / 5.61
Declared Cooling Capacity
20°C Pdc
kW
721.5 / 601.2
770.7 / 630.9
804.6 / 664.7
838.4 / 698.6
Declared EER
d
20°C
6.65 / 6.65
6.80 / 6.79
6.84 / 6.84
6.87 / 6.88
Sound Power Level L
dB(A)
92.27
92.95
93.48
93.95
Air fl ow rate
m³/h
419338.21
419338.21
419338.21
419338.21
Off mode P
OFF
0.15
0.15
0.15
0.15
Thermostat-off mode P
TO
2.14
2.45
2.65
2.86
Standby Mode P
SB
0.35
0.35
0.35
0.35
Crankcase heater mode P
CK
0.00
0.00
0.00
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Technical Data
Ecodesign - DCC (RQ)
Notes Units
DCC064TR-18PXXX
DCC076TR-17SXYY
DCC084TR-18SYYY
DCC087TR-18SYVV
SEPR
1, 3, 5
6.17
5.90
5.90
5.74
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
767869.72
959289.29
1057261.38
1122993.48
Rated Refrigerant Capacity P
A
1, 3, 5
kW
639.60
763.50
841.90
870.10
Rated Power Input D
A
kW
192.65
243.15
266.42
286.22
Rated EER
DC,A
3.32
3.14
3.16
3.04
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
625.4 / 549.3
739.1 / 641.4
823.1 / 723.3
848.0 / 742.7
Declared Power Input D
B
kW
138.0 / 119.2
172.4 / 146.2
191.8 / 165.5
203.4 / 174.0
Declared EER
DC,B
4.53 / 4.61
4.29 / 4.39
4.29 / 4.37
4.17 / 4.27
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
594.0 / 511.8
692.6 / 610.4
780.8 / 673.1
797.2 / 690.7
Declared Power Input D
C
kW
98.3 / 82.7
120.7 / 104.3
136.8 / 115.0
143.0 / 121.3
Declared EER
DC,C
6.05 / 6.19
5.74 / 5.85
5.71 / 5.85
5.57 / 5.70
Declared Refrigerant Capacity
P
D
kW
523.2 / 435.9
628.3 / 515.6
693.6 / 577.9
709.4 / 589.1
Declared Power Input D
D
kW
73.4 / 61.3
91.0 / 74.5
100.3 / 83.6
105.4 / 87.3
Declared EER
DC,D
7.12 / 7.11
6.91 / 6.92
6.92 / 6.91
6.73 / 6.75
SSCEE
2, 3, 5
%
194
185
183
182
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
640.00
764.00
842.50
870.60
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
639.60
763.50
841.90
870.10
Declared EER
d
35°C
3.32
3.14
3.16
3.04
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
625.4 / 549.3
739.1 / 641.4
823.1 / 723.3
848.0 / 742.7
Declared EER
d
30°C
4.53 / 4.61
4.29 / 4.39
4.29 / 4.37
4.17 / 4.27
Declared Cooling Capacity
25°C Pdc
kW
594.0 / 511.8
692.6 / 610.4
780.8 / 673.1
797.2 / 690.7
Declared EER
d
25°C
6.05 / 6.19
5.74 / 5.85
5.71 / 5.85
5.57 / 5.70
Declared Cooling Capacity
20°C Pdc
kW
523.2 / 435.9
628.3 / 515.6
693.6 / 577.9
709.4 / 589.1
Declared EER
d
20°C
7.12 / 7.11
6.91 / 6.92
6.92 / 6.91
6.73 / 6.75
Sound Power Level L
dB(A)
88.44
89.96
90.34
91.71
Air fl ow rate
m³/h
419338.21
396041.64
419338.21
419338.21
Off mode P
OFF
0.15
0.15
0.15
0.15
Thermostat-off mode P
TO
1.31
1.89
2.60
2.05
Standby Mode P
SB
0.35
0.34
0.35
0.35
Crankcase heater mode P
CK
0.00
0.00
0.00
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od
esi
gn
116
Chillers
DeltaChill
TM
DeltaChill Technical Manual 9758541 V1.1_06_2020