Technical Data
Ecodesign - DCC (RQ)
Notes Units
DCC033DR-08KLR0
DCC036DR-08KRR0
DCC043DR-08LXX0
DCC043DR-08KSS0
SEPR
1, 3, 5
6.99
6.78
5.88
6.39
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
346685.00
394789.73
537627.42
500361.20
Rated Refrigerant Capacity P
A
1, 3, 5
kW
327.10
361.20
426.50
431.50
Rated Power Input D
A
kW
100.34
113.58
139.38
139.64
Rated EER
DC,A
3.26
3.18
3.06
3.09
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
359.1 / 299.7
396.7 / 336.3
469.0 / 393.4
473.6 / 401.8
Declared Power Input D
B
kW
82.0 / 65.3
93.1 / 76.3
113.9 / 93.1
114.9 / 94.3
Declared EER
DC,B
4.38 / 4.59
4.26 / 4.41
4.12 / 4.23
4.12 / 4.26
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
324.2 / 254.1
364.2 / 297.6
426.6 / 344.8
435.1 / 356.0
Declared Power Input D
C
kW
52.0 / 39.5
60.8 / 47.8
77.0 / 59.8
76.4 / 59.9
Declared EER
DC,C
6.24 / 6.44
5.99 / 6.22
5.54 / 5.77
5.69 / 5.95
Declared Refrigerant Capacity
P
D
kW
271.8 / 179.7
319.0 / 241.8
359.2 / 269.3
381.6 / 289.9
Declared Power Input D
D
kW
28.9 / 19.6
35.3 / 26.3
51.1 / 38.4
46.1 / 34.3
Declared EER
DC,D
9.40 / 9.19
9.03 / 9.21
7.03 / 7.01
8.29 / 8.44
SSCEE
2, 3, 5
%
194
197
179
189
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
327.50
361.50
427.00
432.00
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
327.10
361.20
426.50
431.50
Declared EER
d
35°C
3.26
3.18
3.06
3.09
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
359.1 / 299.7
396.7 / 336.3
469.0 / 393.4
473.6 / 401.8
Declared EER
d
30°C
4.38 / 4.59
4.26 / 4.41
4.12 / 4.23
4.12 / 4.26
Declared Cooling Capacity
25°C Pdc
kW
324.2 / 254.1
364.2 / 297.6
426.6 / 344.8
435.1 / 356.0
Declared EER
d
25°C
6.24 / 6.44
5.99 / 6.22
5.54 / 5.77
5.69 / 5.95
Declared Cooling Capacity
20°C Pdc
kW
271.8 / 179.7
319.0 / 241.8
359.2 / 269.3
381.6 / 289.9
Declared EER
d
20°C
9.40 / 9.19
9.03 / 9.21
7.03 / 7.01
8.29 / 8.44
Sound Power Level L
dB(A)
92.69
93.39
89.16
94.18
Air fl ow rate
m³/h
186372.54
186372.54
186372.54
186372.54
Off mode P
OFF
0.08
0.08
0.14
0.08
Thermostat-off mode P
TO
1.27
1.51
1.76
2.02
Standby Mode P
SB
0.13
0.13
0.25
0.13
Crankcase heater mode P
CK
0.11
0.13
0.00
0.13
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od
esi
gn
107
Chillers
DeltaChill
TM
DeltaChill Technical Manual 9758541 V1.1_06_2020