Technical Data
Ecodesign - DCC (RQ)
Notes Units
DCC045DR-08KSQ0
DCC033DR-10KLR0
DCC037DR-10KRR0
DCC043DR-10LXX0
SEPR
1, 3, 5
6.28
7.35
7.17
6.06
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
525149.03
333955.31
378066.72
528420.42
Rated Refrigerant Capacity P
A
1, 3, 5
kW
445.10
331.10
365.80
432.20
Rated Power Input D
A
kW
144.98
97.10
109.52
134.22
Rated EER
DC,A
3.07
3.41
3.34
3.22
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
415.8 / 298.9
363.1 / 302.7
401.5 / 340.0
474.8 / 397.9
Declared Power Input D
B
kW
98.4 / 65.9
78.9 / 63.0
89.4 / 73.5
109.5 / 89.7
Declared EER
DC,B
4.23 / 4.54
4.60 / 4.81
4.49 / 4.63
4.34 / 4.43
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
447.7 / 320.1
327.3 / 256.3
368.0 / 300.2
431.3 / 348.1
Declared Power Input D
C
kW
79.1 / 54.0
49.7 / 37.8
57.9 / 45.8
74.3 / 57.9
Declared EER
DC,C
5.66 / 5.93
6.59 / 6.77
6.35 / 6.56
5.80 / 6.01
Declared Refrigerant Capacity
P
D
kW
477.4 / 340.6
271.8 / 180.2
320.2 / 242.4
359.2 / 269.2
Declared Power Input D
D
kW
59.4 / 41.7
27.6 / 18.8
33.1 / 24.9
50.5 / 38.1
Declared EER
DC,D
8.03 / 8.17
9.87 / 9.57
9.66 / 9.74
7.11 / 7.06
SSCEE
2, 3, 5
%
186
202
204
185
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
445.60
331.40
366.20
432.70
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
445.10
331.10
365.80
432.20
Declared EER
d
35°C
3.07
3.41
3.34
3.22
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
415.8 / 298.9
363.1 / 302.7
401.5 / 340.0
474.8 / 397.9
Declared EER
d
30°C
4.23 / 4.54
4.60 / 4.81
4.49 / 4.63
4.34 / 4.43
Declared Cooling Capacity
25°C Pdc
kW
447.7 / 320.1
327.3 / 256.3
368.0 / 300.2
431.3 / 348.1
Declared EER
d
25°C
5.66 / 5.93
6.59 / 6.77
6.35 / 6.56
5.80 / 6.01
Declared Cooling Capacity
20°C Pdc
kW
477.4 / 340.6
271.8 / 180.2
320.2 / 242.4
359.2 / 269.2
Declared EER
d
20°C
8.03 / 8.17
9.87 / 9.57
9.66 / 9.74
7.11 / 7.06
Sound Power Level L
dB(A)
95.96
92.53
93.19
87.66
Air fl ow rate
m³/h
186372.54
232965.67
232965.67
232965.67
Off mode P
OFF
0.08
0.08
0.08
0.14
Thermostat-off mode P
TO
2.18
1.35
1.50
1.91
Standby Mode P
SB
0.13
0.14
0.14
0.26
Crankcase heater mode P
CK
0.11
0.11
0.13
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od
esi
gn
109
Chillers
DeltaChill
TM
DeltaChill Technical Manual 9758541 V1.1_06_2020