Technical Data
Ecodesign - DCF (XQ)
Notes Units
DCF091TX-21R
YYY
DCF094TX-18R
YVV
DCF096TX-18R
VVV
DCF099TX-18R
VVW
SEPR
1, 3, 5
6.79
6.52
6.56
6.47
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
907642.63
988553.15
1019660.22
1065636.88
Rated Refrigerant Capacity P
A
1, 3, 5
kW
831.20
870.20
902.40
930.00
Rated Power Input D
A
kW
264.71
299.04
311.17
327.46
Rated EER
DC,A
3.14
2.91
2.90
2.84
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
820.0 / 721.7
867.7 / 766.4
903.5 / 800.8
927.2 / 824.5
Declared Power Input D
B
kW
191.2 / 165.6
212.6 / 182.0
222.0 / 191.1
229.4 / 198.6
Declared EER
DC,B
4.29 / 4.36
4.08 / 4.21
4.07 / 4.19
4.04 / 4.15
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
780.7 / 672.9
826.9 / 719.9
865.5 / 750.8
895.7 / 781.1
Declared Power Input D
C
kW
137.6 / 116.3
150.8 / 128.5
157.9 / 132.8
164.2 / 139.1
Declared EER
DC,C
5.67 / 5.79
5.49 / 5.60
5.48 / 5.65
5.45 / 5.61
Declared Refrigerant Capacity
P
D
kW
664.2 / 575.8
695.3 / 617.0
721.1 / 648.0
743.1 / 666.3
Declared Power Input D
D
kW
66.6 / 86.0
73.0 / 93.1
75.2 / 96.1
79.5 / 98.4
Declared EER
DC,D
9.98 / 6.70
9.52 / 6.63
9.59 / 6.74
9.34 / 6.77
SSCEE
2, 3, 5
%
176
167
172
170
SSCEE Tier
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
831.90
871.10
903.30
930.90
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
831.20
870.20
902.40
930.00
Declared EER
d
35°C
3.14
2.91
2.90
2.84
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
820.0 / 721.7
867.7 / 766.4
903.5 / 800.8
927.2 / 824.5
Declared EER
d
30°C
4.29 / 4.36
4.08 / 4.21
4.07 / 4.19
4.04 / 4.15
Declared Cooling Capacity
25°C Pdc
kW
780.7 / 672.9
826.9 / 719.9
865.5 / 750.8
895.7 / 781.1
Declared EER
d
25°C
5.67 / 5.79
5.49 / 5.60
5.48 / 5.65
5.45 / 5.61
Declared Cooling Capacity
20°C Pdc
kW
664.2 / 575.8
695.3 / 617.0
721.1 / 648.0
743.1 / 666.3
Declared EER
d
20°C
9.98 / 6.70
9.52 / 6.63
9.59 / 6.74
9.34 / 6.77
Sound Power Level L
dB(A)
88.17
89.32
89.86
90.29
Air fl ow rate
m³/h
302214.45
259040.95
259040.95
259040.95
Off mode P
OFF
0.15
0.15
0.15
0.15
Thermostat-off mode P
TO
4.50
5.76
5.50
5.91
Standby Mode P
SB
0.36
0.35
0.35
0.35
Crankcase heater mode P
CK
0.00
0.00
0.00
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.