Technical Data
Ecodesign - DCF (XQ)
Notes Units
DCF045DX-10LXX0
DCF060DX-12MYY0
DCF062DX-12MYV0
DCF054DX-13MXY0
SEPR
1, 3, 5
6.72
6.68
6.62
6.96
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
459379.19
614076.49
642244.69
533868.55
Rated Refrigerant Capacity P
A
1, 3, 5
kW
416.60
553.30
574.20
501.60
Rated Power Input D
A
kW
136.14
182.61
195.31
155.29
Rated EER
DC,A
3.06
3.03
2.94
3.23
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
389.1 / 315.9
518.2 / 422.4
538.0 / 441.5
554.7 / 455.1
Declared Power Input D
B
kW
91.4 / 71.7
122.9 / 96.1
128.4 / 101.5
127.5 / 101.9
Declared EER
DC,B
4.25 / 4.41
4.22 / 4.40
4.19 / 4.35
4.35 / 4.47
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
422.8 / 342.1
562.7 / 456.6
582.4 / 475.4
492.6 / 406.7
Declared Power Input D
C
kW
75.9 / 59.5
102.0 / 79.9
106.4 / 84.2
84.8 / 68.7
Declared EER
DC,C
5.57 / 5.75
5.52 / 5.72
5.47 / 5.65
5.81 / 5.92
Declared Refrigerant Capacity
P
D
kW
332.7 / 264.9
442.0 / 354.6
458.7 / 365.4
400.6 / 301.2
Declared Power Input D
D
kW
33.7 / 39.3
45.1 / 52.5
46.9 / 54.4
39.2 / 44.1
Declared EER
DC,D
9.87 / 6.75
9.81 / 6.76
9.78 / 6.72
10.22 / 6.83
SSCEE
2, 3, 5
%
173
175
172
177
SSCEE Tier
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
417.20
553.90
574.90
502.30
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
416.60
553.30
574.20
501.60
Declared EER
d
35°C
3.06
3.03
2.94
3.23
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
389.1 / 315.9
518.2 / 422.4
538.0 / 441.5
554.7 / 455.1
Declared EER
d
30°C
4.25 / 4.41
4.22 / 4.40
4.19 / 4.35
4.35 / 4.47
Declared Cooling Capacity
25°C Pdc
kW
422.8 / 342.1
562.7 / 456.6
582.4 / 475.4
492.6 / 406.7
Declared EER
d
25°C
5.57 / 5.75
5.52 / 5.72
5.47 / 5.65
5.81 / 5.92
Declared Cooling Capacity
20°C Pdc
kW
332.7 / 264.9
442.0 / 354.6
458.7 / 365.4
400.6 / 301.2
Declared EER
d
20°C
9.87 / 6.75
9.81 / 6.76
9.78 / 6.72
10.22 / 6.83
Sound Power Level L
dB(A)
86.25
86.22
87.26
86.42
Air fl ow rate
m³/h
143911.64
172693.97
172693.97
187085.13
Off mode P
OFF
0.14
0.14
0.14
0.14
Thermostat-off mode P
TO
2.64
3.22
3.60
3.42
Standby Mode P
SB
0.26
0.27
0.27
0.28
Crankcase heater mode P
CK
0.00
0.00
0.00
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Technical Data
Ecodesign - DCF (XQ)
Notes Units
DCF061DX-14MYY0
DCF046DX-12LXX0
DCF047DX-12KSS0
DCF049DX-12KSQ0
SEPR
1, 3, 5
6.85
6.89
7.66
7.49
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
611990.23
458508.46
418733.19
441087.56
Rated Refrigerant Capacity P
A
1, 3, 5
kW
565.70
426.60
432.70
445.60
Rated Power Input D
A
kW
177.34
132.07
134.80
140.13
Rated EER
DC,A
3.19
3.23
3.21
3.18
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
625.5 / 525.4
471.5 / 395.0
405.7 / 334.0
418.7 / 302.0
Declared Power Input D
B
kW
145.4 / 119.7
108.1 / 89.0
91.5 / 72.1
95.5 / 65.0
Declared EER
DC,B
4.30 / 4.39
4.36 / 4.44
4.44 / 4.63
4.38 / 4.65
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
569.7 / 459.7
427.6 / 344.7
439.2 / 359.6
451.1 / 323.0
Declared Power Input D
C
kW
99.7 / 78.2
73.9 / 58.1
73.8 / 58.6
76.3 / 53.1
Declared EER
DC,C
5.72 / 5.88
5.78 / 5.93
5.95 / 6.13
5.91 / 6.08
Declared Refrigerant Capacity
P
D
kW
451.9 / 354.7
340.6 / 265.0
345.5 / 291.6
355.8 / 343.0
Declared Power Input D
D
kW
45.4 / 52.1
34.2 / 39.1
27.0 / 34.0
28.8 / 41.1
Declared EER
DC,D
9.95 / 6.80
9.96 / 6.78
12.82 / 8.58
12.35 / 8.35
SSCEE
2, 3, 5
%
180
178
186
182
SSCEE Tier
Tier 2 (2021)
Tier 1 (2018)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
566.40
427.20
433.40
446.30
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
565.70
426.60
432.70
445.60
Declared EER
d
35°C
3.19
3.23
3.21
3.18
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
625.5 / 525.4
471.5 / 395.0
405.7 / 334.0
418.7 / 302.0
Declared EER
d
30°C
4.30 / 4.39
4.36 / 4.44
4.44 / 4.63
4.38 / 4.65
Declared Cooling Capacity
25°C Pdc
kW
569.7 / 459.7
427.6 / 344.7
439.2 / 359.6
451.1 / 323.0
Declared EER
d
25°C
5.72 / 5.88
5.78 / 5.93
5.95 / 6.13
5.91 / 6.08
Declared Cooling Capacity
20°C Pdc
kW
451.9 / 354.7
340.6 / 265.0
345.5 / 291.6
355.8 / 343.0
Declared EER
d
20°C
9.95 / 6.80
9.96 / 6.78
12.82 / 8.58
12.35 / 8.35
Sound Power Level L
dB(A)
86.41
86.43
86.96
87.49
Air fl ow rate
m³/h
201476.30
172693.97
156881.71
156881.71
Off mode P
OFF
0.14
0.14
0.08
0.08
Thermostat-off mode P
TO
3.17
2.59
3.53
3.80
Standby Mode P
SB
0.28
0.27
0.15
0.15
Crankcase heater mode P
CK
0.00
0.00
0.13
0.11
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.