Technical Data
Ecodesign - DCC (RQ)
Notes Units
DCC032DR-06KLR0 DCC036DR-06KRR0 DCC022DR-08JJK0 DCC027DR-08KKL0
SEPR
1, 3, 5
6.47
6.27
7.35
7.11
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
368337.67
419319.92
213483.03
282554.21
Rated Refrigerant Capacity P
A
1, 3, 5
kW
321.80
355.00
211.70
271.10
Rated Power Input D
A
kW
104.82
118.73
60.49
79.04
Rated EER
DC,A
3.07
2.99
3.50
3.43
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
353.5 / 295.4
390.2 / 331.1
232.0 / 169.9
297.4 / 221.8
Declared Power Input D
B
kW
86.2 / 68.5
98.2 / 80.4
48.6 / 33.7
64.4 / 46.0
Declared EER
DC,B
4.10 / 4.31
3.98 / 4.12
4.77 / 5.04
4.62 / 4.83
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
319.8 / 250.9
358.6 / 293.7
251.1 / 182.7
239.2 / 167.9
Declared Power Input D
C
kW
55.2 / 41.9
64.9 / 50.6
37.9 / 26.6
36.6 / 25.3
Declared EER
DC,C
5.80 / 5.99
5.53 / 5.80
6.63 / 6.86
6.54 / 6.62
Declared Refrigerant Capacity
P
D
kW
269.5 / 178.7
315.0 / 239.6
194.6 / 138.9
254.6 / 178.5
Declared Power Input D
D
kW
31.5 / 20.7
38.3 / 28.3
20.3 / 14.9
26.9 / 19.6
Declared EER
DC,D
8.56 / 8.63
8.23 / 8.45
9.60 / 9.31
9.47 / 9.12
SSCEE
2, 3, 5
%
184
187
208
200
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
322.10
355.40
212.10
271.40
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
321.80
355.00
211.70
271.10
Declared EER
d
35°C
3.07
2.99
3.50
3.43
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
353.5 / 295.4
390.2 / 331.1
232.0 / 169.9
297.4 / 221.8
Declared EER
d
30°C
4.10 / 4.31
3.98 / 4.12
4.77 / 5.04
4.62 / 4.83
Declared Cooling Capacity
25°C Pdc
kW
319.8 / 250.9
358.6 / 293.7
251.1 / 182.7
239.2 / 167.9
Declared EER
d
25°C
5.80 / 5.99
5.53 / 5.80
6.63 / 6.86
6.54 / 6.62
Declared Cooling Capacity
20°C Pdc
kW
269.5 / 178.7
315.0 / 239.6
194.6 / 138.9
254.6 / 178.5
Declared EER
d
20°C
8.56 / 8.63
8.23 / 8.45
9.60 / 9.31
9.47 / 9.12
Sound Power Level L
dB(A)
93.14
93.88
89.29
91.62
Air fl ow rate
m³/h
139779.40
139779.40
186372.54
186372.54
Off mode P
OFF
0.08
0.08
0.08
0.08
Thermostat-off mode P
TO
1.27
1.44
0.82
0.95
Standby Mode P
SB
0.12
0.12
0.13
0.13
Crankcase heater mode P
CK
0.11
0.13
0.09
0.09
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od
esi
gn
106
Chillers
DeltaChill
TM
DeltaChill Technical Manual 9758541 V1.1_06_2020