DeltaChill Technical Manual 9758541 V1.1_06_2020
Chillers
DeltaChill
TM
Technical Data
DCC Regular Quiet
Mechanical Data
Notes Units
DCC064TR-
18PXXX
DCC076TR-
17SXYY
DCC084TR-
18SYYY
DCC087TR-
18SYVV
DCC089TR-
18SVVV
DCC094TR-
18SVVW
Capacity
Number of Refrigeration Circuits
3
3
3
3
3
3
Cooling Duty - EC Fans
(1)
kW
640.0
764.0
842.5
870.6
889.6
935.2
Nominal Input - Mechanical
kW
191.7
241.6
264.4
284.7
295.3
309.7
EER
(2)
3.34
3.16
3.19
3.06
3.01
3.02
ESEER (Gross)
4.87
4.67
4.68
4.55
4.48
4.53
ESEER (Net)
4.74
4.54
4.51
4.44
4.37
4.40
Nominal Output - Free Cooling
kW
N/A
N/A
N/A
N/A
N/A
N/A
Ambient temperature for 100% Free Cooling (5)
°C
N/A
N/A
N/A
N/A
N/A
N/A
Capacity Steps
% 11-23-34-45-56-
67-78-89-100
10-22-34-44-
56-68-77-88-
100
11-23-34-45-57-
68-78-89-100
11-23-34-45-56-
68-78-89-100
12-23-35-46-
57-68-78-89-
100
11-22-35-45-56-
68-78-89-100
Minimum Turndown Ratio
0.11
0.10
0.11
0.11
0.12
0.11
Dimensions (HxW)
mm
2682x2200
Length
mm
10506
10506
10506
10506
10506
10506
Machine Weight
(3)
kg
6850
6985
7085
7075
7075
7150
Operating Weight
kg
7140
7280
7375
7365
7365
7440
Evaporator
Shell and Tube
Water Volume (Total Internal)
l
132.1
383.9
370.1
370.1
370.1
357.0
Maximum Waterfl ow
l/s
57.2
56.3
56.3
74.9
74.9
74.9
Minimum Waterfl ow
l/s
14.8
13.9
14.1
18.8
18.8
19.0
Condenser
Face Area (Total)
m²
42.75
40.38
42.75
42.75
42.75
42.75
Nominal Airfl ow
m³/s
116.48
110.01
116.48
116.48
116.48
116.48
Condenser Fan & Motor
Quantity
18
17
18
18
18
18
Diameter
mm
800
800
800
800
800
800
Maximum Speed
rpm
1026
1026
1026
1026
1026
1026
Compressor
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Quantity of Compressors
9
9
9
9
9
9
Oil Charge Volume (Total)
l
3x5.3 + 3x5.3 +
3x5.3
3x5.3 +
3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
Oil Type
Polyvinyl Ether
Refrigeration
GWP Equivalent CO
2
Tonnes
tCO
2
61.43
65.48
71.55
71.55
71.55
74.25
Charge (Total)
kg
29 + 31 + 31 28 + 34 + 35 34 + 35 + 37
34 + 35 + 37
34 + 35 + 37
35 + 37 + 38
Maximum Allowable Pressure High Side (PS)
barg
40.2
40.2
40.2
40.2
40.2
40.2
Maximum Allowable Pressure Low Side (PS)
barg
24.5
24.5
24.5
24.5
24.5
24.5
Connections
Water Inlet / Outlet - Unit
DN150
DN150
DN150
DN150
DN150
DN150
Water System
Minimum System Water Volume
(4)
l
1252.01
1265.34
1657.24
1637.16
1753.57
1783.42
Nominal Water Flow
l/s
30.46
36.36
40.10
41.43
42.34
44.51
Pressure drop
kPa
19.31
24.47
32.95
21.35
21.86
24.46
Electrical Data
Nominal Run Amps
(6)
A
480.4
554.9
596.0
616.9
637.3
657.7
Maximum Start Amps
A
753
827
862
882
896
916
Recommended Mains Fuse Size
A
560
630
630
670
670
710
Recommended Permanent Fuse Size
A
16
16
16
16
16
16
Maximum Permanent Incoming Cable Size
mm²
4
4
4
4
4
4
Evaporator Heater Rating
W
170
250
250
250
250
250
Condenser Fan - Per Fan (EC)
Full Load Amps
A
3.9
3.9
3.9
3.9
3.9
3.9
Motor Rating
kW
2.56
2.56
2.56
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
40.7 / 40.7 /
53.7
53.7 / 53.7 /
53.7
53.7 / 60.4 /
60.4
60.4 / 60.4 /
60.4
60.4 / 60.4 /
67.3
60.4 / 67.3 /
67.3
Quantity
(7)
3
3
3
3
3
3
Motor Rating
kW
25.9 / 25.9 /
33.6
33.6 / 33.6 /
33.6
33.6 / 36.5 /
36.5
36.5 / 36.5 /
36.5
36.5 / 36.5 /
41.3
36.5 / 41.3 /
41.3
Start Amps
(8)
A
210 / 210 / 326 326 / 326 /
326
326 / 326 / 326 326 / 326 / 326 326 / 326 / 295 326 / 295 / 295
(1)
Based on AC units performance at 12/7°C return/supply temperatures, 35°C ambient, 100% water. All performance data is supplied in accordance
with BS EN 14511-1:2018.
(2)
EER = DX Cooling Output / (Compressor input power + Fan Input Power).
(3)
Based on standard unit without options, operating weight includes refrigerant charge and water volume. For unit weights with waterside options fi tted
please refer to Airedale.
(4)
For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations.
(5)
Ambient temperature that full Freecool capacity can be achieved.
(6)
EC fans and no pumps.
(7)
Data quoted at design fl ow-rate, 7°C supply temperature and 35°C ambient, 100% water.
(8)
Starting amps refers to the direct on line connections.
Pump electrical data is available from Airedale upon request.