Installation Data
Unit Lifting
●
Employ lifting specialists.
●
Local codes and regulations relating to the lifting of this type of equipment should be observed.
●
Use the lifting eye bolts/lifting lugs provided.
●
Attach lifting chains to each of the lifting eye bolts/lifting lugs provided; each chain and eye bolt must be capable
of lifting the whole chiller.
●
Use the appropriate spreader bars/lifting slings with the holes/lugs provided.
●
Lift the unit slowly and evenly.
●
If the unit is dropped, it should immediately be checked for damage and reported to Airedale.
●
Allow free space above the fans to prevent air recirculation.
Lifting Dimensions
4 Point
A
≥
A
The unit should be lifted from the base and where possible, with all packing and protection in
position. If any other type of slinging is used, due care should be taken to ensure that the slings do
not crush the casework or coil.
CAUTION
Number of Fans
Brazed Plate Evaporator
Shell and Tube Evaporator
Lifting Eyebolt
Size
A (mm)
Lifting Lug
Size (mm)
A (mm)
4
M24
1850
-
-
6
M30
2186
-
-
7-8
M30
3502
35
3680
9 - 10
M30
3336
35
4415
11-12
M36
4745
35
3145
13-14
-
-
35
4077
15-16
-
-
35
4750
17-18
-
-
35
5730
19-20
-
-
35
6660
21
-
-
35
6930