Benchmark 6000 Boiler Installation, Operation & Maintenance Manual
CHAPTER 5 – MODE OF OPERATION
Page
76
of
210
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0086_0D
03/20/14
Ph.: 800-526-0288
GF-133
applications. It is suggested that AERCO be contacted prior to changing settings other than the
unit’s setpoint. For a complete listing of temperature related function defaults, see Appendix E.
To set the unit to the manual mode, press the
AUTO/MAN
switch. The
MANUAL
LED will light.
To set the unit back to the auto mode, press the
AUTO/MAN
switch. The
MANUAL
LED will go
off and the
REMOTE
LED will light.
When the boiler is switched to ACS control, the ACS controls the valve position. There are no
setup requirements to the boiler(s) in this mode.