Benchmark 6000 Boiler Installation, Operation & Maintenance Manual
APPENDIX D – INDOOR/OUTDORR RATIO CHARTS
Page
164
of
210
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0086_0D
03/20/14
Ph.: 800-526-0288
GF-133
Table D-3: Header Temperature for a Building Reference Temperature of 65ºF
RESET RATIO
Air
Temp
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
65
65
65
65
65
65
65
65
65
65
65
60
68
69
70
71
72
73
74
75
76
77
55
71
73
75
77
79
81
83
85
87
89
50
74
77
80
83
86
89
92
95
98
101
45
77
81
85
89
93
97
101
105
109
113
40
80
85
90
95
100
105
110
115
120
125
35
83
89
95
101
107
113
119
125
131
137
30
86
93
100
107
114
121
128
135
142
149
25
89
97
105
113
121
129
137
145
153
161
20
92
101
110
119
128
137
146
155
164
173
15
95
105
115
125
135
145
155
165
175
185
10
98
109
120
131
142
153
164
175
186
197
5
101
113
125
137
149
161
173
185
197
209
0
104
117
130
143
156
169
182
195
208
-5
107
121
135
149
163
177
191
205
219
-10
110
125
140
155
170
185
200
215
-15
113
129
145
161
177
193
209
-20
116
133
150
167
201
218
Table D-4: Header Temperature for a Building Reference Temperature of 70ºF
RESET RATIO
Air
Temp
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
70F
70
70
70
70
70
70
70
70
70
70
65F
73
74
75
76
77
78
79
80
81
82
60F
76
78
80
82
84
86
88
90
92
94
55F
79
82
85
88
91
94
97
100
103
106
50F
82
86
90
94
98
102
106
110
114
118
45F
85
90
95
100
105
110
115
120
125
130
40F
88
94
100
106
112
118
124
130
136
142
35F
91
98
105
112
119
126
133
140
147
154
30F
94
102
110
118
126
134
142
150
158
166
25F
97
106
115
124
133
142
151
160
169
178
20F
100
110
120
130
140
150
160
170
180
190
15F
103
114
125
136
147
158
169
180
191
202
10F
106
118
130
142
154
166
178
190
202
214
5F
109
122
135
148
161
174
187
200
213
0F
112
126
140
154
168
182
196
210
-5F
115
130
145
160
175
190
205
-10F
118
134
150
166
182
198
214
-15F
121
138
155
172
189
206
-20F
124
142
160
178
196
214