Benchmark 6000 Boiler Installation, Operation & Maintenance Manual
APPENDIX A – BOILER MENU DESCRIPTIONS
OMM-0086_0D
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
149
of
210
GF-133
Ph.: 800-526-0288
03/20/14
APPENDIX A – BOILER MENU ITEM DESCRIPTIONS
MENU LEVEL & OPTION
DESCRIPTION
OPERATING MENU
Active Setpoint
This is the setpoint temperature to which the control
is set when operating in the Constant Setpoint,
Remote Setpoint or Outdoor Reset Mode. When in
the Constant Setpoint Mode, this value is equal to
the Internal Setpoint setting in the Configuration
Menu. When in the Remote Setpoint Mode, this
value is the setpoint equivalent to the remote analog
signal supplied to the unit. When in the Outdoor
Reset Mode, this is the derived value from the charts
in Appendix D.
Inlet Water Temp
Displays the inlet water temperature in ºF or ºC.
Default is ºF
Air Temp
Air Temp is the air temperature at the input to the
Air/Fuel Valve. This reading is one of the parameters
used to control the Blower Motor speed.
Outdoor Temp
Outdoor temperature is displayed in ºF (default) or ºC
only if outdoor sensor is installed and enabled.
Valve Position In
Desired input valve position. This would normally be
the same as the fire valve position shown on the
bargraph (valve position out) when the boiler is
operating.
Exhaust Temp
Displays the exhaust temperature in °F (default), or
ºC.
Flame Strength
Displays flame strength from 0% to 100%.
Oxygen Level
Displays the real-time combustion oxygen (O
2
) level
(%) measured by the O
2
sensor.
Run Cycles
Displays the total number of run cycles from 0 to
999,999.
Run Hours
Displays total run time of unit in hours from 0 to
9,999,999.
Fault Log
Displays information on the last 20 faults.