Benchmark 6000 Boiler Installation, Operation & Maintenance Manual
CHAPTER 6 – SAFETY DEVICE TESTING
Page
84
of
210
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0086_0D
03/20/14
Ph.: 800-526-0288
GF-133
Figure 6-4: Blower Proof Switch & Blocked Inlet Switch Locations
6.8.1 Blower Proof Switch Test
Blower Proof Switch
Test
1. Disable the blower output drive voltage as follows:
a) Press the
MENU
key until
CONFIGURATION MENU
is displayed.
b)
Press the ▲ arrow key until the
ANALOG OUTPUT
function is displayed, then press
the
CHANGE
key.
c)
Press the ▼ arrow key until
OFF
is displayed, then press the
ENTER
key.
2. Start the unit in the Manual Mode at a valve position between 25% and 30%.
3. The unit should shut down and Lockout, showing
AIRFLOW FAULT DURING PURGE
in
the display.
4. The unit should perform one
IGNITION RETRY
cycle and then shut down, since the blower
is disabled. The unit will then display
AIRFLOW FAULT DURING PURGE
.
5. Re-enable the blower output drive voltage by performing the following steps:
a) Press the
MENU
key until
CONFIGURATION MENU
is displayed.
b)
Press the ▲ arrow key until the
ANALOG OUTPUT
function is displayed, then press
the
CHANGE
key.
c)
Press the ▲ arrow key until
VALVE POSITION 0-10V
is displayed, then press the
ENTER
key.
d) Press the
CLEAR
button to clear the airflow fault.
6. Once the unit has proved flame, turn off the blower again by going to the Configuration
Menu, Analog Output menu item and select
OFF
.
7. The Blower Proof Switch will open and the blower should stop. The unit should shut down
and display
AIRFLOW FAULT DURING RUN
.
BLOCKED INLET
SWITCH
BLOWER PROOF
SWITCH
AIR/FUEL VALVE
ASSEMBLY
MANUAL SHUT-
OFF VALVE
BLOWER