APPENDIX M – LONG TERM BLOWER STORAGE
Page
204
of
210
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0086_0D
03/20/14
Ph.: 800-526-0288
GF-133
LONG-TERM STORAGE INSTRUCTIONS (Cont.)
5. General Motor Procedure:
If the motor is not put into service immediately, the motor must be stored in a clean, dry,
warm location. Minimum temperature of 50°F. (10°C,). Several precautionary steps must
be performed to avoid motor damage during storage.
a) Use a “Megger” each month to ensure that integrity of the winding insulation has been
maintained. Record the Megger readings. Immediately investigate any significant drop
in insulation resistance.
b) DO NOT lubricate the motor bearings during storage. Motor bearings are packed
with grease at the factory.
c) If the storage location is damp or humid, the motor windings must be protected
from moisture. This can be done by applying power to the motor’s space heaters,
(IF AVAILABLE) while the motor is in storage. If the motor does not have space
heaters, storing it in a damp or humid location will, very quickly, cause internal
corrosion and motor failure which is not warranted.
NOTE
For specific storage instructions, for the actual motor and any accessory
parts that were supplied, refer to the manufacturer’s instructions.
Figure M-1: Benchmark 6000 Blower Exploded View
1. INLET FLANGE
2. INLET-SIDE PLATE
3. INLET-SIDE HOUSING
4. BLOWER WHEEL
5. DRIVE-SIDE HOUSING
6. DRIVE-SIDE PLATE
7. BASE, FAN
8. MOTOR
9. RISER BLOCKS *
10. RISER BASE *
* IF REQUIRED